Meaning:
Draining is not properly done
In this case:
When this message appears, the cylinder is drained, the general fault contact is activated, and the device is stopped.
Causes and remedies:
1.
The drain system is clogged. Press the manual drain button, and check for the proper flow of water. Then clean
the inside of the cylinder. Check if there is limestone in the valve.
Alarm
P8
Information "CLEAN CY DRAIN VALVE"
TO CARRY OUT A RESET FOR THE ABOVE
MESSAGES, FOLLOW THIS PROCEDURE:
-Switch the unit to drain by pressing the manual drain button (4).
-Press button 3 for at least 5 seconds.
5
1
2
3
4
TEMP. (°C) SENSOR
FAULTY
TEMP. (°C) SENSOR
MISSING
Defective probe (thermal shock) or incorrect probe
installation
Connection problem between the temperature sensor
and connector X04 (15-16-17) on the main board
Or Wrong configuration of the dip switchs
S4 , S5, S6