3.8.4
MODBUS RTU and BACNET MSTP communication parameters
Modbus RTU
Bacnet MSTP
Speed of communication
2400 / 4800 / 7200 / 9600 (default) / 14400 / 19200 / 28800 / 38400 / 57600 /
115200 / 230400
Packet size
8 bits
Parity Bit
Not
Stop bit
2
1
Timeout response
5000ms (5sec)
Time between requests
(After a response received)
Min. 100ms
Standard
3.8.5
Communication protocol for RS485 interface - MODBUS and BACNET
Modbus
Register
Address
Bacnet Object
Class / instance # / ID
(hex)
Description
Value
10001
BI
0
00C00000
Contactor
1 = production -- 0 = no production
10002
BI
1
00C00001
High-level detection
1 = reached-- 0 = no reached
10003
BI
2
00C00002
High limit switch
1 is opened -- 0 is closed
10004
BI
3
00C00003
Fill valve
1 = filling
–
0 = no filling
10005
BI
4
00C00004
Drain valve
1 = draining -- 0 : no draining
10006
BI
5
00C00005
relay X10 (term. 3-4): Blower pack
/ remote ON/OFF, service, default
1 : relay ON -- 0 : relay OFF
10007
BI
6
00C00006
maintenance returns
1 is ON -- 0 is OFF
10008
BI
7
00C00007
Alarm returns
1 is ON -- 0 is OFF
1
BO
0
01000000
On/Off BMS command
1 = ON : Start requested / 0 = Off: Stop Unit
2
Bv
1
01400001
Not used
Not used
3
Bv
2
01400002
option 1 (with SB card 8 relays)
1: ON -- 0: OFF
4
Bv
3
01400003
option 2 (with SB card 8 relays)
1: ON -- 0: OFF
5
Bv
1
01400001
option 3 (with SB card 8 relays)
1: ON -- 0: OFF
6
Bv
2
01400002
option 4 (with SB card 8 relays)
1: ON -- 0: OFF
30001
Have
0
00000000
Type unit
1: Steam Bath, 2: ELMC,3: CMC, 13: EHU 750
30002
Have
1
00000001
Register version
1
30003
Have
2
00000002
Current
10 x (A)
Summary of Contents for ElectroVap ELMC 20-30 SB
Page 1: ...STEAM GENERATOR FOR STEAM ROOM ElectroVap ELMC SB Series Instruction Operation Manual ...
Page 25: ...ElectroVap ELMC SB 25 3 8 6 Wiring diagrams ELMC 5 to 10 Up V 1x200 240V 50 60Hz ...
Page 26: ...ElectroVap ELMC SB 26 ELMC 5 to 30 Up V 3x200 690V 50 60Hz ...
Page 27: ...ElectroVap ELMC SB 27 ELMC 40 to 60 Up V 3x200 690V 50 60Hz ...
Page 28: ...ElectroVap ELMC SB 28 ELMC 90 Up V 3x200 690V 50 60Hz ...
Page 29: ...ElectroVap ELMC SB 29 3 9 OPTION Transformer connection ...
Page 51: ...ElectroVap ELMC SB 51 ...