With " AUTO " selected,
indication is automatically changed every
th ree (3) seconds,
- 1 - E n g in e S peed
R e v o lu tio n s p e r m in u te is in d icated .
1500m in
~ 1 is
in d icated at 5 0 H z and 1800 m in
"
1 is in d icated at 60H z.
- 2 - Engine Oil Pressure
2 to 5
X
100 kPa ( 2 to 5 kg / cm! ) should be indicated at normal
engine operation.
Higher value would be indicated in cold condition
immediately after engine starts.
Conduct a warming - up operation
until it indicates normal value.
- 3 - Hun Hours
That indicated total running hours.
- 4 - Battery Charging Voltage
That should indicate more than 26V (25USI‘USI2, 45USTUSl2:more than
12. 5V) at engine running.
- 5 - Engine Coolant Tem perature
That should indicate a tem perature between 75 to 90 tC at engine running.
Note ; If that would indicate higher temperature,
disconnect all loads,
decrease the speed for cool - down operation,
and wait until the
tem perature comes down to normal value.
- 6 - Automatic Indication Change
Each of the above - started indications from the - I - to - 5 - changes by turns
every 3 seconds.
(2)
Fuel Level Indicator
That Indicates a fuel level in the fuel tank.
Green lamps will turn on with full tank.
As the fuel level drops,
the numbers of the turn - on lamps decrease and at the
sametim e the color of lamps changes from green to red.
Replenish the tank when there becomes only one lamp turned on.
The table below shows the relation between numbers of turn - on lamps and feul level.