Complete the Wiring Connections
The following connections must be completed to install the
ELITE
pro
XC
. ALL WORK SHOULD BE
PERFORMED BY A QUALIFIED ELECTRICIAN USING PROPER SAFETY EQUIPMENT.
CAUTION: The ELITE
pro
XC should only be wired by qualified personnel. Hazardous voltages exist.
ATTENTION: LE ELITE
pro
XC ne doit être branché QUE par un personnel qualifié. TENSIONS
DANGEREUSES sont présentEs.
CT
C
ONNECTIONS
NOTE:
Use only inherently safe 333mV output CTs supplied by DENT. Never use current output CTs. The
UL listing covers the use of the following DENT Instruments CTs that are UL Recognized and have been
evaluated to IEC 61010-1:
CT-HSC-020-X (20A Mini), CT-HSC-050-X (50A Mini), CT-HMC-0100-X (100A Midi), and the CT-HMC-0200-
X (200A Midi). The use of any other CT will invalidate the UL Listing of the
ELITE
pro
XC
.
1) Connect the CTs to the channel(s) on the
ELITE
pro
XC
labeled CH 1, CH 2, CH 3 and CH 4. The CT
leads need to be connected to the terminal block using a small screwdriver. For R
ō
Coils, also
connect the shield (bare) wires to the right-most ground terminal marked “S” (shield).
2) Place the CTs on the phase wires of the load to be monitored and corresponding to the phase of the
voltage loads. The CTs must be placed as follows for each channel:
Left connector pin is the positive or high-side wire
Right pin is the negative or low-side
When using DENT Instruments current transformers, connect them as follows:
Split-core CTs (removable leg)—the white CT wire is (+) and the black wire is (-).
Clamp-on CTs (clothes-pin type)—the red wire is positive (+) and the black wire is negative (-).
R
ō
Coil CTs (flexible, Rogowski-style)—the white CT wire is (+) and the brown wire is (-).
If you are using R
ō
Coil CTs, be sure to connect the bare wire to the “S” (shield) screw terminal. This
reduces interference and improves the accuracy of the CT.
www.
.com
1.800.561.8187
Summary of Contents for ELITEpro XC
Page 58: ...58 Typical Single Phase 2 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Page 59: ...59 Typical Single Phase 3 Wire Setup Diagram www com information itm com 1 800 561 8187 ...
Page 60: ...60 Typical 3 Phase 3 Wire Delta Setup Diagram www com information itm com 1 800 561 8187 ...
Page 61: ...61 Typical 3 Phase 4 Wire Wye Setup Diagram www com information itm com 1 800 561 8187 ...