Page 8
4. Digital Inputs (counters)
Figure 5.
Location of the digital inputs
DAEnetIP4
IP controller (the core of the current module) supports 8 digital inputs
every of which is combined with 16 bit cyclic counter. These inputs are extended with
Schmitt triggers in this module so they are able to handle voltages from 0 up-to 30V
DC. Moreover every digital input can control digital output (relay) and send traps up-
on falling and/or rising edge of the input signal. For more information please refer to
the
DAEnetIP4's
documentation here:
http://denkovi.com/Documents/DAEnetIP4/Current-Version/UserManual.pdf
Table 3. Digital inputs electrical characteristics
Type
Peripheral board
Digital inputs count
8
Nominal value of inputs
Voltage
Current
VDC
mA
12
5.2
Max non desctructive voltage
VDC
30.0
Input switching limit values
From 0 to 1 Voltage
Current
From 1 to 0 Voltage
Current
VDC
mA
VDC
mA
>7.6
>3.2
<4.5
<1.8
Input impedance at state 1
kΩ
2.2
Sensor compability
2-wire
3-wire
Yes PNP
No
Input type
Resistive with Schmitt
trigger
Isolation
Between supply and
inputs
Between inputs
No
No
Protection
Against reverse polarity
Yes
Table 4. Mapping to
DAEnetIP4
JP2 digital inputs (counters) port
Digital input pin # (DAEnetIP4 JP2)
Digital Input # (peripheral board)
Digital Input #1 (JP2.1)
Din1
Digital Input #2 (JP2.2)
Din2
Digital Input #3 (JP2.3)
Din3
Digital Input #4 (JP2.4)
Din4
Digital Input #5 (JP2.5)
Din5
Digital Input #6 (JP2.6)
Din6
Digital Input #7 (JP2.7)
Din7