Chapter 5 Parameters
|
VFD-B-P Series
5-42
Revision April 2009, SW V1.00
Group 3: Output Function Parameters
03 - 00
Multi-function Output Relay (RA1, RB1, RC1)
Factory Setting: 08
03 - 01
Multi-function Output Terminal MO1
Factory Setting: 01
03 - 02
Multi-function Output Terminal MO2
Factory Setting: 02
03 - 03
Multi-function Output Terminal MO3
Factory Setting: 20
Settings Function
Description
00 No
Function
01
AC Drive Operational
Active when there is an output from the drive or RUN
command is “ON”.
02
Master Frequency
Attained
Active when the AC motor drive reaches the output
frequency setting.
03 Zero
Speed
Active when Command Frequency is lower than the
Minimum Output Frequency.
04 Over-Torque
Detection
Active as long as over-torque is detected. (Refer to Pr.06-03
~ Pr.06-05)
05
Baseblock (B.B.)
Indication
Active when the output of the AC motor drive is shut off
during baseblock. Base block can be forced by Multi-function
input (setting 9 or 10).
06
Low-Voltage Indication
Active when low voltage(Lv) is detected.
07
Operation Mode
Indication
Active when operation command is controlled by external
terminal.
08 Fault
Indication
Active when faults occur (oc, ov, oH, oL, oL1, EF, cF3, HPF,
ocA, ocd, ocn, GFF).
09
Desired Frequency
Attained 1
Active when the desired frequency (Pr.03-04) is attained.
10
PLC Program Running
Active when PLC Program is running.
11
PLC Program Step
Completed
Active for 0.5 sec each time the multi-step speed is attained.
12
PLC Program Completed
Active for 0.5 sec when the PLC program cycle has
completed