Appendix B Accessories
|
VFD-B-P Series
Revision April 2009, SW V1.00
B-25
a) Please use a shield cable to prevent interference. Do not run control wire parallel to
any high voltage AC power line (200V and up).
b) Connect shielded wire to
E only.
c) Recommended wire size 0.21 to 0.81mm
2
(AWG24 to AWG18).
d) Wire
length:
The Output Types of
the Encoder
Maximum Wire
Length
Wire Gauge
Output Voltage
50m
Open Collector
50m
Line Driver
300m
Complementary 70m
1.25mm
2
(AWG16) or above
3. Control Terminals Block Designations.
OC
TP
A/O
B/O
0V
12V
0V
A
A
B
Connect to the
Series Control Board
VFD
Select the input
power and the
output type of the
Encoder
PG-03
FSW2
B
G
B
A