Chapter 5 Parameters
|
VFD-B-P Series
Revision April 2009, SW V1.00
5-39
This parameter determines the response of the drive when power is on and the operation
command source is changed.
Pr.02-06
Start lockout (Run when power is ON)
Operation status when operation
command source is changed
00
Disable (AC motor drive will run)
Keep previous status
01
Enable (AC motor drive won’t run)
Keep previous status
02
Disable (AC motor drive will run)
Change according to the new
operation command source
03
Enable (AC motor drive won’t run)
Change according to the new
operation command source
When the operation command source is from an external terminal and operation command is
ON (FWD/REV-DCM=close), the AC motor drive will operate according to Pr.02-06 after
power is applied.
<For terminals FWD and REV only>
1. When Pr.02-06 is set to 00 or 02, AC motor drive will run immediately.
2. When Pr.02-06 is set to 01 or 03, AC motor drive will remain stopped until operation
command is received after previous operation command is cancelled.
RUN
RUN
STOP
STOP
Pr.02-01=1 or 2
This action will follow FWD/DCM
or REV/DCM status
(ON is close/OFF is open)
ON
OFF
FWD-DCM (close)
Pr.02-01=0
output frequency
Pr.02-06=2 or 3
Change operation
command source
output frequency
Pr.02-06=0 or 1
When the operation command source isn’t from the external terminals, independently from
whether the AC motor drive runs or stops, the AC motor drive will operate according to Pr.02-
06 if the two conditions below are both met.
1. When operation command source is changed to external terminal (Pr.02-14=1 or 2)
2.
The status of terminal and AC motor drive is different.