52
test steps are as follows:
A.
In block [1], click on
, and after adding the BACnet/IP device, you can see that the serial
number is 12 characters long (such as 2034C0012844) and the default Device Instance
260001 UNOcentral is in block [1]. Next, click on the UNOcentral item and the provided
BACnet objects will be displayed.
B.
Click the BACnet object in block [2], and the detailed data of the object, including
Presented Value, will be displayed in block [3].
C.
Right-click on the BACnet object in block [2], and use the right-click function menu to
subscribe to the displayed value of the object. If the object does not support the
subscription function, it will be realized by period grabbing. Successfully subscribed
objects will be displayed in block [4], and the first subscription value may take a short time
to update.
Note: The actual serial number is different for each UNOcentral, and the Device Instance is
decided by the settings in 2.1.1.5 BACnet/IP settings each chapter.