40
2.1.2.3
Sensor
Figure 27 Sensor tab
As shown in Figure 27, the Sensor Settings tab can be used to set the threshold for
UNOnext to automatically control the equipment for air quality. The UNOnext sensor
threshold and its default value can be set. As shown in Table 18:
Table 18
Default values and units of UNOnext sensor control
Sensor
Default value
Unit
Carbon dioxide (CO
2
)
1000
ppm
PM2.5
35
μg/m
3
PM10
75
μg/m
3
Total volatile organic compounds (TVOC)
0.56
ppm
Formaldehyde (HCHO)
0.08
ppm
Carbon monoxide (CO)
9
ppm
Ozone (O
3
)
0.06
ppm
After the setting is completed, click [Update] for it to take effect.
When UNOnext runs as Turbo mode, if the real-time value of any of the sensors in the
above table exceeds the set threshold, UNOnext will activate the ventilation equipment, and
will not shut down until the real-time sensor data of these sensors fall below 90% of the