28
automation standard protocol BACnet/IP. On the BACnet/IP tab, you can set the unique Device
Instance of the BACnet/IP server in the subnet, as shown in Figure 16. Fill in the Device Instance
to be set. The default value is 260001. Press [Update] and wait for a short period of time (about
30 seconds) for it to take effect. The information provided by UNOcentral through BACnet/IP
will be described in the appendix 3 Description of BACnet/IP data.
Figure 16 BACnet/IP settings tab
Note: BACnet/IP uses port 47808 and the UDP protocol to communicate on the internal
network. It is recommended to adjust the Server address and Port access restrictions and
firewall rules with the network manager or IT personnel to ensure that it can operate
normally.
2.1.1.6
Schedule settings
The scheduling function means that by defining the control plan of UNOcentral,
UNOcentral will calculate control methods for all UNOnext devices to operate the ventilation
equipment. The smallest unit of the control plan is the schedule formed by [Date Combination]
[Time Period] [Enable Control]. A control plan can consist of up to 4 schedules, and each
UNOcentral can set up to 4 control plans.