48
Example:
http://[IP]:8888/signage.html?id=208&lang=zh-tw
http://[IP]:8888/signage.html?id=208&lang=en
Globalview:
http://[IP]:8888/globalview.html?lang=zh-tw
Note: Parameters of
display mode
and
mandatory language setting
are url parameters.
Parameter can be con
catenated, the first parameter is marked by “?”, following
parameters are marked by “&”, all parameters are set value by “=”.
Additionally,
language switch button will be not worked when using mandatory language settings.
3.
Description of BACnet/IP data
After setting and confirming the BACnet/IP Device Instance of UNOcentral (the default is
260001), you can use the BACnet/IP client to read the information provided by UNOcentral
through BACnet/IP, which includes the sensor values of up to 16 connected UNOnext devices
and status of linked ventilation equipment. UNOcentral provides 304 Analog_Input (AI) objects,
48 Binary_Input (BI) objects, 16 Multi_State_Input (MI) objects, for a total of 368 BACnet objects.
Assuming that U represents UNOnext number 00 to 15, the UNOnext number corresponds to
the UNOnext connected in RS485 mode and UNOnext WiFi in MQTT mode; see Table 20.
Table 20
Table of corresponding UNOnext BACnet numbers
UNOnext BACnet number
UNOnext Modbus ID (RS485)
UNOnext WiFi ID (MQTT)
00
208
1
01
209
2
02
210
3
03
211
4
04
212
5
05
213
6