Operation and installation manual SOLIVIA 5.0 EU G3
The fi rst line shows the limits according the standard. The second line shows the actual measured
grid voltage and the test status, positive (pass) or negative (fail). Pressing the test is confi rmed
and the auto-test routine continue. If no is pressed, the result is shown for 1minute. After this
time, the result is confi rmed automatically.
The fi rst line shows the limits according the standard. The second line shows the actual measured
grid frequency and the test status, positive (pass) or negative (fail). Pressing the test is confi rmed
and the auto-test routine continue. If no is pressed, the result is shown for 1minute. After this
time, the result is confi rmed automatically.
The fi rst line shows the actual high frequency limit and detection time settings according to the
standards. Since the protection is not sensitive to the frequency variations less than 40 ms (two
line cycles of the grid voltage at nominal frequency of 50 Hz), the detection time has been set to
60 ms. Pressing the test starts. Test starts also automatically after 1 minute if no is pressed.
The fi rst line shows the actual low frequency limit and detection time settings according to the
standards. Since the protection is not sensitive to the frequency variations less than 40 ms (two line
cycles of the grid voltage at nominal frequency of 50 Hz), the detection time has been set to 60 ms.
Pressing the test starts. Test starts also automatically after 1 minute if no is pressed.
If has been pressed the display shows, for example:
The limit “L:” will increase till crossing the actual measured grid voltage “A:”. Reached this condition
the inverter display shows, for example:
L: 230 V 0.164 S
A: 230 V UV pass
If the test is confi rmed, the inverter performs the HFT test, high frequency test, which verify the high
frequency protection. The display shows:
L: 50.30 Hz < 0.06 S
Start HFT test?
L: 50.30 Hz HFT
A: 49.99 Hz RUN
The limit “L:” will decrease till crossing the actual measured grid frequency “A:”. Reached this con-
dition the inverter display shows, for example:
L: 49.99 Hz 0.044 S
A: 49.99 Hz HF pass
If the test is confi rmed, the inverter performs the LFT test, low frequency test, which verify the low
frequency protection. The display shows:
L: 49.70 Hz < 0.06 S
Start LFT test?
Summary of Contents for SOLIVIA 5.0
Page 1: ...Operation and installation manual for SOLIVIA 5 0 EU G3 5 0 EU...
Page 2: ......
Page 4: ...2 Operation and installation manual SOLIVIA 5 0 EU G3...
Page 40: ...38 Bedienungsanleitung SOLIVIA 5 0 EU G3 Bedienungsanleitung SOLIVIA 5 0 EU G3...
Page 42: ...40 Bedienungsanleitung SOLIVIA 5 0 EU G3 Bedienungsanleitung SOLIVIA 5 0 EU G3...
Page 78: ...76 Manuale di istruzioni SOLIVIA 5 0 EU G3...
Page 80: ...78 Manuale di istruzioni SOLIVIA 5 0 EU G3...
Page 192: ...190 Manual de instru es SOLIVIA 5 0 EU G3...
Page 194: ...192 Manual de instru es SOLIVIA 5 0 EU G3...
Page 230: ...228 N vod k obsluze SOLIVIA 5 0 EU G3...
Page 232: ...230 N vod k obsluze SOLIVIA 5 0 EU G3...
Page 306: ...304 Handleiding SOLIVIA 5 0 EU G3 Handleiding SOLIVIA 5 0 EU G3...
Page 308: ...306 Handleiding SOLIVIA 5 0 EU G3 Handleiding SOLIVIA 5 0 EU G3...
Page 344: ...342 SOLIVIA 5 0 EU G3...
Page 346: ...344 SOLIVIA 5 0 EU G3...
Page 351: ...349 SOLIVIA 5 0 EU G3 4 3 1 2 3 RS485 EIA485 4 5 3 1 2 4 3 5...
Page 359: ...357 SOLIVIA 5 0 EU G3 6 9 Solar Inverter MPP Booster DC Bus DC DC DC DC A B C D AC...
Page 378: ...376 SOLIVIA 5 0 EU G3 DC 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 5 0...
Page 381: ...379 SOLIVIA 5 0 EU G3 12 https guarantee solar inverter com SOLIVIA 5 10 5...
Page 382: ...380 Operation and installation manual SOLIVIA 5 0 EU G3 13 Certificates...
Page 383: ...381 Operation and installation manual SOLIVIA 5 0 EU G3...
Page 390: ...388 Operation and installation manual SOLIVIA 5 0 EU G3 Notes...
Page 391: ......