10
Operation and installation manual SOLIVIA 5.0 EU G3
6.5
Ambient temperature
The solar inverter can be operated in an ambient temperature between -25 °C to +60 °C.
The following diagram illustrates how the power supplied by the solar inverter is reduced automa-
tically in accordance with ambient temperature.
The device should be installed in a well-ventilated, cool and dry location.
6.6
Grid connection
The grid (AC output) is connected over a Wieland RST25i3S AC connector. You can find the cor-
rect allocation on the screw-type terminal connection of the connector. The solar inverter must be
connected to the grid over a three-core line (L, N, PE). The connected AC line must be switched
potential-free before the disconnection or the insertion of the AC connector.
The connection to the Wieland AC connector must be made with a flexible line and a conductor
cross section of 4.0 mm².
An automatic circuit breaker is to be provided in the line L upstream of every device, with a nominal
current of 32 A and tripping characteristic type B. In addition, attention is to be paid to the selectivity
of the fuse unit attached upstream of the automatic circuit breaker.
The solar inverter must be grounded via the AC connector’s PE conductor. To do this, connect the
PE conductor to the designated terminal. If you wish to integrate more than one inverter into the
installation, please proceed as illustrated in the drawings in the appendix.
Please note the cable length and the cable cross-section, due to the risk of undesirable temperature
rise and power losses.
The AC connector is protected from unintentional disconnection by a clip mechanism which can be
released with a screwdriver.
0
1000
2000
3000
4000
5000
6000
0
10
20
30
40
50
60
70
80
Ambient temperature (°C )
Output power (
W
)
Summary of Contents for SOLIVIA 5.0
Page 1: ...Operation and installation manual for SOLIVIA 5 0 EU G3 5 0 EU...
Page 2: ......
Page 4: ...2 Operation and installation manual SOLIVIA 5 0 EU G3...
Page 40: ...38 Bedienungsanleitung SOLIVIA 5 0 EU G3 Bedienungsanleitung SOLIVIA 5 0 EU G3...
Page 42: ...40 Bedienungsanleitung SOLIVIA 5 0 EU G3 Bedienungsanleitung SOLIVIA 5 0 EU G3...
Page 78: ...76 Manuale di istruzioni SOLIVIA 5 0 EU G3...
Page 80: ...78 Manuale di istruzioni SOLIVIA 5 0 EU G3...
Page 192: ...190 Manual de instru es SOLIVIA 5 0 EU G3...
Page 194: ...192 Manual de instru es SOLIVIA 5 0 EU G3...
Page 230: ...228 N vod k obsluze SOLIVIA 5 0 EU G3...
Page 232: ...230 N vod k obsluze SOLIVIA 5 0 EU G3...
Page 306: ...304 Handleiding SOLIVIA 5 0 EU G3 Handleiding SOLIVIA 5 0 EU G3...
Page 308: ...306 Handleiding SOLIVIA 5 0 EU G3 Handleiding SOLIVIA 5 0 EU G3...
Page 344: ...342 SOLIVIA 5 0 EU G3...
Page 346: ...344 SOLIVIA 5 0 EU G3...
Page 351: ...349 SOLIVIA 5 0 EU G3 4 3 1 2 3 RS485 EIA485 4 5 3 1 2 4 3 5...
Page 359: ...357 SOLIVIA 5 0 EU G3 6 9 Solar Inverter MPP Booster DC Bus DC DC DC DC A B C D AC...
Page 378: ...376 SOLIVIA 5 0 EU G3 DC 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 5 0...
Page 381: ...379 SOLIVIA 5 0 EU G3 12 https guarantee solar inverter com SOLIVIA 5 10 5...
Page 382: ...380 Operation and installation manual SOLIVIA 5 0 EU G3 13 Certificates...
Page 383: ...381 Operation and installation manual SOLIVIA 5 0 EU G3...
Page 390: ...388 Operation and installation manual SOLIVIA 5 0 EU G3 Notes...
Page 391: ......