26
Operation and installation manual SOLIVIA 5.0 AP G3
8
Diagnostics and data evaluation
8.1
Malfunction rectification
The solar inverter is provided with an automatic diagnostics system which independently identifies
certain faults and which can make them visible on the display.
Troubleshooting in the field
In principle, it is always worth attempting a reset by reinitializing the solar inverter whenever an error
message appears on the display.
To reset the device, proceed as follows:
1. Isolate the solar inverter from the grid (open automatic circuit breaker).
2. Switch off the DC disconnector.
3. Wait: approx. 1 minute.
4. Switch DC disconnector back on.
5. Switch in grid (close automatic circuit breaker).
(In the field, the first step is to scan for potential fault causes that could be picked up by the solar
inverter and result in tripping.)
Various key parameters can be scanned via the display, thereby enabling conclusions to be drawn
about potential fault causes.
Current values in the N menu
AC Voltage -> Display of current output voltage -> Voltage limiting values
AC Frequency -> Display of current grid frequency -> Frequency limiting values
Solar Voltage -> Display of current PV cell voltage -> Switch-in threshold
8.2
Display messages
LED STATUS
DISPLAY
MESSAGE
CAUSE
ELIMINATION
green: <on>
red: <on>
yellow: <on>
-
Display communication
faulty.
- If the fault persists after the device has
been reset, please inform your service
technician.
green: <off>
red: <off>
yellow: <on>
AC frequency
failure
Grid frequency overshoo-
ting or undershooting
specified limit range.
- Check the grid frequency via the
display in the N menu.
green: <off>
red: <off>
yellow: <on>
AC voltage
failure
Grid voltage overshooting
or undershooting specified
limit range.
- Check the grid voltage via the display in
the N menu.
- If no voltage present, check grid auto-
matic circuit breaker.
green: <off>
red: <off>
yellow: <on>
AC relay
failure
One of the anti-islanding
protection output relays is
faulty / defective.
- The solar inverter is defective.
- Return the device.
green: <flashes>
red: <off>
yellow: <off>
Calibration
ongoing
Check internal settings.
Normal function before input mode.
green: <off>
red: <off>
yellow: <on>
DC injection
failure
DC component of input-
side alternating current is
too high.
- If the fault persists after the device has
been reset, please inform your service
technician.
green: <off>
red: <off>
yellow: <on>
Error # 301
Internal communication
error or hardware fault.
- If the fault persists after the device has
been reset, please inform your service
technician.
Summary of Contents for SOLIVIA 5.0 AP G3
Page 1: ...Operation and installation manual for SOLIVIA 5 0 AP G3 5 0 AP...
Page 2: ......
Page 4: ...2 Operation and installation manual SOLIVIA 5 0 AP G3...
Page 38: ...36 SOLIVIA 5 0 AP G3...
Page 40: ...38 SOLIVIA 5 0 AP G3...
Page 42: ...40 SOLIVIA 5 0 AP G3 1 SOLIVIA 5 0 AP G3 AC 2 SOLIVIA 5 0 AP G3 9 18kg 5...
Page 43: ...41 SOLIVIA 5 0 AP G3 3 12 IP65 4 MPP 4 1 PC...
Page 44: ...42 SOLIVIA 5 0 AP G3 4 2 DC AC MPP MPP 150V 450V 540 VDC IP65 25 C 60 C RS485 EMC 4 6kVA...
Page 45: ...43 SOLIVIA 5 0 AP G3 4 3 1 2 3 RS485 EIA485 4 5 LED 1 4 5 2 3...
Page 53: ...51 SOLIVIA 5 0 AP G3 6 9 MPP DC DC DC DC DC A AC B C D 51 SOLIVIA 5 0 AP G3...
Page 68: ...66 SOLIVIA 5 0 AP G3 10 10 1 400 220V 400 230 V VNB Z 1 Z 2 1 2 400 220 V 400 230 V 4 6kVA...
Page 69: ...67 SOLIVIA 5 0 AP G3 400 220V 400 230 V VNB Z 1 Z 2 1 2 3 400 220 V 400 230 V 4 6kVA...
Page 71: ...69 SOLIVIA 5 0 AP G3 DC 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 5 0...
Page 73: ...71 SOLIVIA 5 0 AP G3 RJ45 8 RJ Registered Jack RS485 EIA485 DC AC TAB 2000 TAB 2000 2000 DSO...
Page 74: ...72 SOLIVIA 5 0 AP G3...
Page 76: ...74 SOLIVIA 5 0 AP G3...
Page 78: ...76 SOLIVIA 5 0 AP G3 1 SOLIVIA 5 0 AP G3 2 SOLIVIA 5 0 AP G3 9 18 5...
Page 79: ...77 SOLIVIA 5 0 AP G3 3 12 IP65 4 4 1 4 2 MPP Tracking 150V 450V 540V IP65 25 C 60 C...
Page 80: ...78 SOLIVIA 5 0 AP G3 4 3 1 2 3 RS485 EIA485 4 5 LED RS485 EMC 4 6 kVA 4 3 1 4 5 2 3...
Page 88: ...86 SOLIVIA 5 0 AP G3 6 9 1 2 3 Wieland 4 5 6 7 UPV 150V 8 S Setup 7 3 7 6 9...
Page 103: ...101 SOLIVIA 5 0 AP G3 10 10 1 400 220 400 230 VNB Z 1 Z 2 1 2 400 220 400 230 4 6...
Page 104: ...102 SOLIVIA 5 0 AP G3 VNB Z 1 Z 2 Z 3 400 220 400 230 400 220 400 230 4 6 1 2 3...
Page 106: ...104 SOLIVIA 5 0 AP G3 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3 Solivia 5 0...
Page 109: ...107 SOLIVIA 5 0 AP G3...
Page 110: ...108 SOLIVIA 5 0 AP G3...
Page 112: ...110 SOLIVIA 5 0 AP G3...
Page 115: ...113 SOLIVIA 5 0 AP G3 3 12 IP65 4 4 1 4 2 150V 450V 540V IP65 25 C 60 C...
Page 116: ...114 SOLIVIA 5 0 AP G3 4 3 1 4 5 2 3 RS485 EMC 4 6 kVA 1 2 3 RS485 EIA485 4 5 LED...
Page 123: ...121 SOLIVIA 5 0 AP G3 6 9 121 SOLIVIA 5 0 AP G3...
Page 138: ...136 SOLIVIA 5 0 AP G3 10 10 1 Z 1 Z 2...
Page 139: ...137 SOLIVIA 5 0 AP G3 Z 1 Z 2 Z 3...
Page 140: ...138 SOLIVIA 5 0 AP G3 10 2 3 3 Z 3 Z 3 3 3 kWh kWh...
Page 141: ...139 SOLIVIA 5 0 AP G3 1 2 3 L1 N PE L2 N PE L3 N PE L1 N n PE L2 L3...
Page 143: ...141 SOLIVIA 5 0 AP G3 RJ45 RJ RS485 ELA485 TAB 2000 TAB 2000 TAB 2000 DSO...
Page 145: ...143...
Page 146: ...144...
Page 147: ......