47
5 Planning the installation
Planning the installation of type 1+2 AC and DC combination surge protection devices
Installation and operation manual M70A_260 Flex RPI703M26000 EU V1.1 EN 2022-08-02
5.6
Planning the installation of type 1+2 AC
and DC combination surge protection
devices
Related topics
“11.7 Installing/replacing DC surge protection devices”,
page 117
“11.9 Installing/replacing type 2 combined AC surge protection
devices”, page 131
“11.8 Installing/replacing type 1+2 combined AC surge protection
devices”, page 124
The inverter is supplied with pre-installed type 2 AC and DC
surge protection devices. Type 1+2 combined surge protection
devices can be ordered as accessories.
To install the type 1+2 combination surge protection devices,
the inverter must be opened. Therefore, it is best to install the
type 1+2 combined surge protection devices before mounting the
inverter and in a dry environment. The easiest way to do this is
with the inverter horizontal.
Install the combined surge protection devices before connect-
ing the inverter to the grid and solar modules. If the inverter is
already in operation, the replacement is considerably more com-
plicated for safety reasons.
All screws, spring washers and washers of the pre-installed
type 2 surge protection devices must be reused for the type 1+2
combined surge protection devices. Take precautions to ensure
that these parts cannot fall down and get lost during installation!