29
4 Product overview
Type plate and markings
Installation and operation manual M70A_260 Flex RPI703M26000 EU V1.1 EN 2022-08-02
Information on the type plate
Meaning
M70A_260
Delta model name
P/N: RPI703M260000
Delta part number
DC INPUT
DC Input
200–1000 Vdc
DC input voltage range
MPPT 460-800Vdc
MPP input voltage range with full power
MAX Idc: 26A*6 MPPT
Maximum DC input current per MPP tracker
1000 V DC max
Maximum DC input voltage
MAX Isc: 50A*6 MPPT
Maximum DC short-circuit current per MPP tracker
AC OUTPUT
AC Output
220/380, 230/400 Vac
AC nominal voltage
3P3W or 3P4W
The inverter can be connected to 3-phase grids without neutral conductors (3P3W,
3 PE) and 3-phase grids with neutral conductors (3P4W, 3 N +
PE).
50/60 Hz
AC nominal frequency
111.6A max
Maximum AC current
cosφ 0.8ind~0.8cap
Setting range of the power factor cos φ
70kW/70kVA nom
Nominal active power/reactive power
77kW/77kVA max
Maximum active power/reactive power
IP65 (Electronics)
Protection class for the electronics as per EN 60529
Protective Class: I
Safety class as per EN 61140
Over Voltage Category: AC: III / DC: II
Overvoltage category for AC and DC as per EN 50539-11
Made in China
The device was made in China.
VDE-AR-N 4105
The inverter fulfills the requirements of VDE-AR-N 4105.
VDE-AR-N 4110
The inverter fulfills the requirements of VDE-AR-N 4110.
CE mark. By applying this mark, Delta declares that the inverter satisfies the provi
-
sions of the applicable EU directives.