10. Use a voltmeter to check that there is no more voltage at
the AC terminal block.
→
If you detect voltage, open the AC power external load
isolating switch.
→
If you detect no voltage, continue to the next step.
11. Unscrew the AC cable gland.
12. Unscrew the conductors of the AC cable and pull out the
AC cable.
155
13 Replacing the inverter