11.8 Installing/replacing type 1+2 combined AC surge protection devices
Related topics
“11.9.2 Removing type 2 AC surge protection devices”, page 131
11.8.1 Notes
DANGER
Electric shock
Potentially fatal voltages are present in the
inverter during operation. When the inverter
is disconnected from all power sources, this
voltage remains in the inverter for up to 60
seconds.
►
Perform the instructions listed in chap-
ter “10. Disconnecting the inverter from
the power supply before working on it”,
page 93
you start work on the
inverter!
AC surge protection devices are supplied
without screws.
All
screws including spring washers and washers
of the old AC surge protection devices must be
reused for the new AC surge protection devices.
Use an insulated, strongly magnetic screwdriver.
The mounting screws must be pulled out and
inserted against a certain resistance. Make sure
that no screws fall down in the process.
11.8.2 Remove the type 1+2 combined AC surge protection device
1. Unscrew and remove the cover.
11 Replacing or cleaning components, installing accessories
Installing/replacing type 1+2 combined AC surge protection devices
124
Installation and operation manual M70A_260 Flex RPI703M26000 EU V1.1 EN 2022-08-02