46
InfraSuite RowCool Precision Cooling –
Chilled Water
5.7.6 Inquiry of system status
Path:
0DLQ0HQXĺ6WDWXVĺ6\VWHP
12/04/30
Capacity
Supply Air T
Supply Air RH
10:10:00
:25.2KW
:25 C
:50%
Return Air T
Return Air RH
Remote Ch1 T
Remote Ch1 RH
:35 C
:35%
:---- C
:----%
Remote Ch2 T
Remote Ch3 T
Remote Ch4 T
Air Volume
:---- C
:---- C
:---- C
:----CMM
Inquire about the system related information, including
cooling capacity
,
supply air
temperature and humidity
,
return air temperature and humidity
,
remote 1 temperature
and humidity
,
remote 2 temperature
,
remote 3 temperature
,
remote 4 temperature
,
chilled water inlet/ outlet temperature
,
FKLOOHGZDWHUÀRZUDWH
,
ball valve opening
,
ball
valve command
(set the ball-valve opening),
fan command
(set the fan speed),
heater
command
,
KXPLGL¿HUFRPPDQG
,
fan 1~8 failed
,
EPO active
,
¿UHDFWLYH
,
smoke active
,
¿OWHUIDLOHG
,
drain pan full
,
leak active
(enable the leakage detection), and
wire leak open
(water leakage detector has open/ short issues).
NOTE:
Heater command
and
humidifier command
are reserved for HCHICB0
and HCH1DB0 models.
5.7.7 Inquiry/ elimination of event log
Path:
0DLQ0HQXĺ6WDWXVĺ(YHQW/RJ
Number
12/01/01
<003>Exit Manual
Mode
:66/66
10:10:00
Summary of Contents for HCH1850
Page 64: ...5013217901...