InfraSuite RowCool Precision Cooling –
Chilled Water
5.7.2 Set point
Path:
0DLQ0HQXĺ6HWWLQJĺ6HWSRLQW
Supply Air T
: 25 C
y
Supply Air T (temperature)
In the automatic mode, the cooling unit will automatically adjust the fans and three-way
ball valve in accordance with this targeted supply air temperature.
5.7.3 Controller setting
Path:
0DLQ0HQXĺ6HWWLQJĺ&RQWUROOHU
:
:
:
:
Force Mode
P Gain
I Gain
D Gain
OFF
09.00
0.550
0.000
:
:
:
:
Min Flow T
Max Flow T
Fan Step
Group Work
25 C
40 C
10
OFF
:
:
:
Auto Recover
Intelligent
Leak.Cut-Off
ON
ON
OFF
y
Force Mode
When the force mode is enabled, the fans will run at full speed and the three-way ball
valve will fully open, which is generally used for performance testing or at a high heat
load.
If the
STANDBY
LQGLFDWRURQWKHFRQWUROSDQHOÀDVKHVWKHXQLWLVLQWKHIRUFHPRGH