D V P 0 2 T K - S / D V P 0 2 T U - S T e m p e r a t u r e C o n t r o l M o d u l e M a n u a l
2 - 3 2
_2
RS-485 Communication Setting Address = 0x0F09, written value is 0x00XY
Bit2
Stop Bits
0
1-bit (default)
1
2-bit
Bit1~Bit0
Parity
0
Even (default)
1
Odd
2
None
3
Reserved
Data Length
Stop Bits
Parity
Y
value
bit3
bit2
bit1
bit0
Data Bits
Stop Bits
Parity
0: 7
1: 8
0: 1-bit
1: 2-bit
0: Even; 1: Odd;
2: None; 3: reserved
0
0
0
0
0
7
1
even
1
0
0
0
1
7
1
odd
2
0
0
1
0
7
1
none
3
0
0
1
1
7
1
even
4
0
1
0
0
7
2
even
5
0
1
0
1
7
2
odd
6
0
1
1
0
7
2
none
7
0
1
1
1
7
2
even
8
1
0
0
0
8
1
even
9
1
0
0
1
8
1
odd
A
1
0
1
0
8
1
none
B
1
0
1
1
8
1
even
C
1
1
0
0
8
2
even
D
1
1
0
1
8
2
odd
E
1
1
1
0
8
2
none
F
1
1
1
1
8
2
even