D V P 0 2 T K - S / D V P 0 2 T U - S T e m p e r a t u r e C o n t r o l M o d u l e M a n u a l
2 - 4
_2
2.1.3
List of the Control Registers
TU
CR#
TK
Add.
(Hex)
Attribute
Name
Description
Default
#0
000
R
O Model
By default, you can see the model name in the
program and determine whether there is any
extension module.
DVP02TUL-S: H014F
DVP02TUN-S: H024F
DVP02TUR-S: H034F
DVP02TKL-S: H044F
DVP02TKN-S: H054F
DVP02TKR-S: H064F
--
#1
001
R
O Firmware version
Hexadecimal, displaying the current firmware
version, for example the current firmware is 1.02 and
it will display H’0102.
--
#2
002
R
O CH1 PV
Channel current value
--
#3
003
R
O CH2 PV
#4
004
R/W O CH1 SV setups
Channel target value
K0
#5
005
R/W O CH2 SV setups
#6
006
R/W X
CH1 setups to
run/stop an operation
K0: stop
K1: run
K2: pause (programmable)
K0
#7
007
R/W X
CH2 setups to
run/stop an operation
#8
008
R/W X
CH1 Auto tuning
K0: Auto control mode
K1: Auto adjust mode, after adjusting it will switch to
the auto control mode and input the most suitable
parameters, e.g., Kc_Kp, Ti_Ki, Td_Kd and Tf.
K2: Auto adjust mode (enhanced), recommended
when the change in temperature reaches 2 degrees.
Another channel would be turned off automatically
while adjusting, then revert back to the original
channel setting once completed.
K0
#9
009
R/W X
CH2 Auto tuning
#10
00A
R/W X
Setups to switch
pages
CR#11~CR#42: Definitions may vary according to
different setups on the specific page.
K0: Basic setup page for CH1
K1: PID setup page for CH1
K2: Program control setup page for CH1
K3: Pattern 0, 1 setup page for CH1
K4: Pattern 2, 3 setup page for CH1
K5: Pattern 4, 5 setup page for CH1
K6: Pattern 6, 7 setup page for CH1
K7: Automatic PID calculation setup page for CH1
K10: Basic setup page for CH2
K0