C h a p t e r 2 C o n t r o l R e g i s t e r
2 - 5
2_
TU
CR#
TK
Add.
(Hex)
Attribute
Name
Description
Default
K11: PID setup page for CH2
K12: Program control setup page for CH2
K13: Pattern 0, 1 setup page for CH2
K14: Pattern 2, 3 setup page for CH2
K15: Pattern 4, 5 setup page for CH2
K16: Pattern 6, 7 setup page for CH2
K17: Automatic PID calculation setup page for CH2
#11~
#42
-- R/W X
According to each
setup page
Please refer to each setup page.
K0
--
00B
R/W --
Page0
Basic setup page for CH1
--
--
02B
R/W --
Page1
PID setup page for CH1
--
--
04B
R/W --
Page2
Program control setup page for CH1
--
--
06B
R/W O
Page3
Pattern 0, 1 setup page for CH1
--
--
08B
R/W O
Page4
Pattern 2, 3 setup page for CH1
--
--
0AB
R/W O
Page5
Pattern 4, 5 setup page for CH1
--
--
0CB
R/W O
Page6
Pattern 6, 7 setup page for CH1
--
--
291
R/W O
Page7
Automatic PID calculation setup page for CH1
--
--
0EB
R/W O
Page10
Basic setup page for CH2
--
--
10B
R/W O
Page11
PID setup page for CH2
--
--
12B
R/W O
Page12
Program control setup page for CH2
--
--
14B
R/W O
Page13
Pattern 0, 1 setup page for CH2
--
--
16B
R/W O
Page14
Pattern 2, 3 setup page for CH2
--
--
18B
R/W O
Page15
Pattern 4, 5 setup page for CH2
--
--
1AB
R/W O
Page16
Pattern 6, 7 setup page for CH2
--
--
2B1
R/W O
Page17
Automatic PID calculation setup page for CH2
--
#43
24B
X
Error code
Please refer to error code descriptions.
K0
#45
24D
R/W X
User-defined
0x0501: Restore to defaults
0x0502: Settings written on flash
0x0504: RS-485 mode and latched
(parameter/mode/station number)
0x51CC: Manually export
0x51DD
:
Auto export
(the PID will be invalid after switching to manually
export mode.)
CR control can be set up by the analog output of
DVP02TUL-S/DVP02TKL-S and the digital output of
/DVP02TUN-S/DVP02TKR-S/DVP02TKN-S.
DVP02TUL-S/DVP02TKL-S
:
CR#4: CH1 analog output value range K0~K4000
CR#5: CH2 analog output value range K0~K4000
K0