background image

TECHNICAL DATASHEET

 

CliQ II DIN Rail Power Supply 

24V 480W 1 Phase / DRP024V480W1B

□ 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (November 2020, Rev. 07)  

 

14

 

Operating Mode 

 

Redundant Operation

 

 

In order to ensure proper redundant operation for the power 

supply unit (PSU), the output voltage difference between the 

two units must be kept at 0.45~0.50V for 24V supplies. Follow 

simple steps given below to set them up for the redundant 

operation: 

 

Step 1. 

Measure output voltage of PSU 1 and PSU 2. If PSU 1 is the 

master unit, then V

O

 of PSU 1 must be higher than PSU 2. In 

order to set the output voltage, individually connect the power 

supply to 50% of rated load at any line voltage from 85-

264Vac, and set the PSU 1 and PSU 2 output voltage. 

 

Step 2. 

Connect the power supply units PSU 1 and PSU 2 to Vin 1 & 

Vin 2, respectively, of the DRR-20N (or 20A) module shown 

on the diagram on the right.   

 

Step 3. 

Connect the system load from V

out

. Please note that output 

voltage V

out

 from DRR module will be = V

O

 (output voltage of 

power supply) – V

drop

* (in DRR module). 

 

*V

drop

  will vary from 0.60V to 0.90V (Typical 0.65V) depending on the load 

current and surrounding air temperature. 

 

 

**The Signal GND in the DRR module is for the built-in LED and DC OK signals. The 

Output GND terminals from the two PSU’s do not need to be connected to the Signal 

GND terminal. 

 

Fig. 4   Redundant Operation Connection Diagram 

 

 

 

 

 

 

 

Parallel Operation 

 

The power supply units (PSUs) can also be used for parallel 

operation in order to increase the output power. The 

difference in output voltage between the two units must be 

kept to within 25mV of each other. This difference must be 

verified with  the same output load connected independently 

to each unit. 
Parameters such as EMI, inrush current, leakage current, 

PARD, start up time will be different  from those on the 

datasheet, when two units are connected in parallel. The user 

will need to verify that any differences will still allow the two 

power supplies connected in parallel will work properly in their 

product/application. 

 

 

 

 

 

Fig. 5   Parallel Operation Connection Diagram 

 

 

 

 

 

 

 

 

 

Summary of Contents for DRP024V480W1B Series

Page 1: ...pply series from one of the world s leading power supply companies Delta Electronics Group offers output voltage of 24V These products are encased in rugged yet lightweight full aluminium body that ca...

Page 2: ...e 24Vdc 2 Output Voltage Adjustment Range 24 28Vdc Output Current 20 0A continuously operating at 24V 30 0A Power Boost for 5 seconds at 24V refer to the details in the Functions section 40 0A Power B...

Page 3: ...g Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 500 Meters 8 200 ft Shock Test Non Operating IEC 60068 2 27 30G 300m S for a duration of 18ms 1 time per direction 2 times in total Vibra...

Page 4: ...L 62368 1 and CSA C22 2 No 62368 1 File No E191395 CB Scheme IEC 60950 1 IEC 62368 1 Industrial Control Equipment UL cUL listed UL 508 and CSA C22 2 No 107 1 01 File No E315355 CSA CSA C22 2 No 107 1...

Page 5: ...z 2GHz 3V M 80 modulation 1KHz 2GHz 2 7GHz 1V M 80 modulation 1KHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2kV Differ...

Page 6: ...DATASHEET CliQ II DIN Rail Power Supply 24V 480W 1 Phase DRP024V480W1B All parameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com November 2020 Rev 07 6 Bloc...

Page 7: ...nd AC input unless otherwise indicated www DeltaPSU com November 2020 Rev 07 7 Device Description 1 Input terminal block connector 2 Output terminal block connector 3 DC Voltage adjustment potentiomet...

Page 8: ...may run into Over Temperature Protection When activated the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as...

Page 9: ...1 Tilt the unit upwards and insert it onto the DIN rail 2 Push downwards until stopped 3 Press against the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2...

Page 10: ...isk of burns Only plug in and unplug connectors when power is turned off DO NOT insert any objects into the unit Hazardous voltages may be present for up to 5 minutes after the input mains voltage is...

Page 11: ...0 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is t...

Page 12: ...approved on 20A UL and 16A IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above Thus if a...

Page 13: ...it may cause damage to the PSU Short Circuit Protection Auto Recovery The power supply s output OLP OCP function also provides protection against short circuits When a short circuit is applied the out...

Page 14: ...tem load from Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on the...

Page 15: ...arth wire or to the machine ground Fig 7 2 of 3 Phase System Input Operation Connection Diagram 2 of 3 Phase System Input Operation Delta s CliQ II can use on 2 of 3 phase system Please refer to the f...

Page 16: ...environment complying with EN 61000 3 2 is only necessary under special conditions Complying to this standard can have some technical drawbacks such as lower efficiency as well as some commercial asp...

Reviews: