background image

TECHNICAL DATASHEET

 

CliQ II DIN Rail Power Supply 

24V 480W 1 Phase / DRP024V480W1B

□ 

 

 

  

All parameters are specified at 25°C ambient and AC input unless otherwise indicated.

 

  www.DeltaPSU.com (November 2020, Rev. 07)  

 

10

 

Safety Instructions 

 

Vertical Mounting 

           

 

 

  ALWAYS switch mains of input power OFF before connecting and disconnecting the input voltage to the unit. If mains are not 

turned OFF, there is risk of explosion / severe damage. 

 

To guarantee sufficient convection cooling, keep a distance of 50mm (1.97 inch) above and below the device as well as a 

lateral distance of 20mm (0.79 inch) to other units. 

  Note that the enclosure of the device can become very hot depending on the surrounding air temperature and load of the power 

supply. Risk of burns! 

  Only plug in and unplug connectors when power is turned off! 

  DO NOT insert any objects into the unit. 

  Hazardous voltages may be present for up to 5 minutes after the input mains voltage is disconnected. Do not touch the unit during 

this time. 

  The power supplies are built in units and must be installed in a cabinet or room (condensation free environment and indoor 

location) that is relatively free of conductive contaminants. 

  CAUTION: “For use in a controlled environment”. 

 

For DRP024V480W1BA: 

  The power supplies unit must be installed in an IP54 enclosure or cabinet in the final installation. The enclosure or cabinet must 

comply with EN 60079-0 or EN 60079-15. 

  Warning: Explosion Hazard - Substitution of components may impair suitability for Class I, Division 2. 

  Warning: Explosion Hazard - Do not disconnect equipment or adjust potentiometer unless the power has been switched off or the 

area is known to be non-hazardous. 

 

 

Summary of Contents for DRP024V480W1B Series

Page 1: ...pply series from one of the world s leading power supply companies Delta Electronics Group offers output voltage of 24V These products are encased in rugged yet lightweight full aluminium body that ca...

Page 2: ...e 24Vdc 2 Output Voltage Adjustment Range 24 28Vdc Output Current 20 0A continuously operating at 24V 30 0A Power Boost for 5 seconds at 24V refer to the details in the Functions section 40 0A Power B...

Page 3: ...g Humidity 5 to 95 RH Non Condensing Operating Altitude 0 to 2 500 Meters 8 200 ft Shock Test Non Operating IEC 60068 2 27 30G 300m S for a duration of 18ms 1 time per direction 2 times in total Vibra...

Page 4: ...L 62368 1 and CSA C22 2 No 62368 1 File No E191395 CB Scheme IEC 60950 1 IEC 62368 1 Industrial Control Equipment UL cUL listed UL 508 and CSA C22 2 No 107 1 01 File No E315355 CSA CSA C22 2 No 107 1...

Page 5: ...z 2GHz 3V M 80 modulation 1KHz 2GHz 2 7GHz 1V M 80 modulation 1KHz Electrical Fast Transient Burst IEC 61000 4 4 Level 3 Criteria A1 2kV Surge IEC 61000 4 5 Level 3 Criteria A1 Common Mode2 2kV Differ...

Page 6: ...DATASHEET CliQ II DIN Rail Power Supply 24V 480W 1 Phase DRP024V480W1B All parameters are specified at 25 C ambient and AC input unless otherwise indicated www DeltaPSU com November 2020 Rev 07 6 Bloc...

Page 7: ...nd AC input unless otherwise indicated www DeltaPSU com November 2020 Rev 07 7 Device Description 1 Input terminal block connector 2 Output terminal block connector 3 DC Voltage adjustment potentiomet...

Page 8: ...may run into Over Temperature Protection When activated the output voltage will go into bouncing mode and will recover when the surrounding air temperature is lowered or the load is reduced as far as...

Page 9: ...1 Tilt the unit upwards and insert it onto the DIN rail 2 Push downwards until stopped 3 Press against the bottom front side for locking 4 Shake the unit slightly to ensure that it is secured Fig 2 2...

Page 10: ...isk of burns Only plug in and unplug connectors when power is turned off DO NOT insert any objects into the unit Hazardous voltages may be present for up to 5 minutes after the input mains voltage is...

Page 11: ...0 to 90 of its final steady state set value Hold up Time Time between the collapse of the AC input voltage and the output falling to 95 of its steady state set value Inrush Current Inrush current is t...

Page 12: ...approved on 20A UL and 16A IEC branch circuits without additional protection device An external protection device is only required if the supplying branch has an ampacity greater than above Thus if a...

Page 13: ...it may cause damage to the PSU Short Circuit Protection Auto Recovery The power supply s output OLP OCP function also provides protection against short circuits When a short circuit is applied the out...

Page 14: ...tem load from Vout Please note that output voltage Vout from DRR module will be VO output voltage of power supply Vdrop in DRR module Vdrop will vary from 0 60V to 0 90V Typical 0 65V depending on the...

Page 15: ...arth wire or to the machine ground Fig 7 2 of 3 Phase System Input Operation Connection Diagram 2 of 3 Phase System Input Operation Delta s CliQ II can use on 2 of 3 phase system Please refer to the f...

Page 16: ...environment complying with EN 61000 3 2 is only necessary under special conditions Complying to this standard can have some technical drawbacks such as lower efficiency as well as some commercial asp...