2) The trigger threshold
Act above
(high tripping point)
: when the measurement
increases
,
it represents the threshold (
ACTIVE ABOVE
in the menu) that shifts the relay from de-
energised to energised when exceeded. The contacts 5-6 and 8-9 will close, the contacts
6-7 and 9-10 will open. The trigger threshold can be disabled.
3) The trigger threshold
Act below
(low tripping point)
: when the measurement
decreases
,
it represents the threshold (
ACTIVE BELOW
in the menu) that shifts the relay from de-
energised to energised when exceeded. The contacts 5-6 and 8-9 will close, the contacts
6-7 and 9-10 will open. The trigger threshold can be disabled.
4) The hysteresis value applies to both thresholds defined above (
Hysteresis
in the menu).
The hysteresis prevents the relay from toggling between the states when the
measurement comes close to the set threshold. The relay is energised when the
measurement reaches one of the two trigger thresholds. When the measurement returns
toward the value of the set threshold, the relay does not shift on the threshold value but
on the threshold
hysteresis value
.
Notes
:
a) You can disable the hysteresis, but we recommend to maintain it to avoid any
malfunctioning near the relay trigger point.
b) The hysteresis width should be lesser than the difference between the two trigger
thresholds
Act above
(high threshold)
and
Act below
(low threshold).
c) If the
Act above
(high)
threshold is
lesser than the
Act below (low)
threshold, the
hysteresis works contrariwise: the relay
de-energises
when the measurement exceeds
the threshold and not, as in the opposite case, the threshold
the hysteresis.
5) Behaviour of the relay if the associate physical quantity goes in error (
ON ERROR
in the
menu).
a) The error can occur when the measurement exceeds the functioning limits indicated in
the technical information,
b) When the probe becomes faulty or gets disconnected.
c) Selecting “
ON ERROR = Inactive
”, in case of error of the controlled quantity, the relay
de-energises.
d) Selecting “
ON ERROR = Active
”, in case of error of the controlled quantity, the relay
energises.