25
G.2 Analog output configuration
The three physical quantities associated to the A1, A2 and A3 analog outputs appear,
respectively, in the first, second and third line of the display
.
The three dip-switches on the card above the terminals 14, 15 and 16, allow to select if the
output is a
current “Idc”
or
voltage “Vdc”
, per each analog output.
To set the three analog outputs, select the “
CONF. OUT
>>
Output Analog 1-2-3”
menu item
.
The following screen will appear:
OUTPUT 1 - 2 - 3
Analog Output 1
Analog Output 2
Analog Output 3
Current/Voltage out
<UP> <DOWN> select
<ENTER> confirm
<ESC> exit/cancel
The “
Current/Voltage out
” function allows to select the type of analog output:
“
0...20mA/0...10Vdc
” or “
4...20mA/2...10Vdc
”.
Selecting “
0...20mA/0...10Vdc
”, the output is 0...20mA if the dip-switch on the card is set
to “Idc” or 0...10Vdc if the dip-switch on the card is set to “Vdc”.
Selecting “
4...20mA/2...10Vdc
”, the output is 4...20mA if the dip-switch on the card is set
to “Idc” or 2...10Vdc if the dip-switch on the card is set to “Vdc”.
OUTPUT 1 - 2 - 3
CURRENT/VOLTAGE OUTPUT
*
4...20mA/2...10Vdc
0...20mA/0...10Vdc
<UP> <DOWN> select
<ENTER> confirm
<ESC> exit/cancel
The active mode is indicated by an asterisk (“
4...20mA/2...10Vdc
” in the example): to set the
other mode, use the
arrows to select it and press ENTER. The asterisk will indicate your
new selection.
Press ESC to return to the previous menu.