Delta Elektronika SM15K Series Product Manual Download Page 7

MASTER SLAVE 

 

SM15K INTERFACES 

7 / 19 

DELTA ELEKTRONIKA B.V. 

rev. Nov. 2019 

 

o

 

The Master has a specific location in the system, depending 
on the number of Slaves. Although in a later stage the 
functional assigned is done via the unit's menu, it is required 
to do the physical assignment first; at which location will the 
Master be and at which the Slave(s). 

o

 

For an uneven number of units, position the Master in 
between an equal number of slaves.  

o

 

For example in a set of 7 units, the upper 3 units must be 
slaves, the master in position 4, and below it another 3 
slaves. 

o

 

For an even number of units, position the master in such a 
way that under it there's 1 slave more than above it. 

o

 

For example in a set of 8 units, the upper 3 units must be 
slaves, then the master, and below it another 4 slaves. 

o

 

See the 

M/S application note

  for more details. 

 

 

Connect the copper strips. 

o

 

See example drawings for different number of units in the 

M/S application note

See fig 3 - 2. 

o

 

Remove safety covers from the DC power terminals. 

o

 

Remove the M8 bolts from the DC power terminals. 

o

 

Important: follow the exact order of washers, lock washers, 
etc. to ensure correct and safe operation. 

o

 

Use the thin crinkle washer "M8 SZ DIN137B" between the 
bolt head and the terminals for maximum isolation distance 
b and -. This replaces one of the standard flat 
washers. 

o

 

Use one of the standard flat washer "M8 A2 DIN125A" + 
lock washer "M8 A2 DIN127B" between the strips and the 
"M8 A2 DIN934" nuts. 

o

 

Note: for easy assembly, first insert the bolts with crinkle 
washers in all 

–DC power terminals. Then assemble the 

 strip to the +DC power terminals. This because 
bolts cannot be inserted in the 

–DC power terminals once 

the + strip is in place. 
 

 

Connect the load cables. 

o

 

The load cables must be connected as close as possible to 
the master at the position indicated on the drawings in the 
application note.  

o

 

When a second set of load cables is required, connect them 
to the Slave below the Master. 

o

 

Place the lugs directly on the strips - never place a washer 
between a cable lug and a copper strip because it will burn 
out. 

o

 

Place the special M/S parallel safety covers over the output 
terminals.  

o

 

Cover with marking DWG2532 is for the outputs of the 
upper and lower units. Cover DWG2533 is for units in 
between them. 

o

 

Create openings for the load cables where necessary. 

3.4.3

 

DC POWER CONNECTIONS FOR M/S-SERIES 

 

It is strongly advised to use one of the M/S SER kits from 
Delta Elektronika for best and safest results! 

o

 

These kits include special copper bars, bolts, nuts, specific 
washers, patch cables and extra safety covers. 

o

 

The basic kit M/S SER SET BA is for 2 units.  

o

 

For each extra unit, an extra kit M/S SER SET BB is 
required. 

o

 

Download the 

M/S application note

 or contact factory for 

more information. 
 

 

Place all the units in a 19 inch rack. 

o

 

Remove the input covers from the units. 

o

 

Remove the mains supply cables. 

o

 

Insert the units in the rack. 

o

 

Stack the units with minimum spacing in between them.  

o

 

Distance between sets of output terminals is 3U = 
133.35mm. 
 

 

Assign a unit as Master. 

 

 

fig 3 - 2 

Examples of DC-connections for Parallel and Series 

operation are available in the M/S application notes. 

Summary of Contents for SM15K Series

Page 1: ...on P0120 Contents 1 Safety Instructions 2 Sicherheitshinweise 3 Master Slave Interface 4 Isolated Contacts 5 Serial Interface 6 Digital User I O 7 Isolated Analog Interface Firmware Update It is stron...

Page 2: ...nd either the minus or plus DC power terminal is grounded the voltage on the DC power terminals and sense connections can be considered safe Caution 1 If a low voltage unit has both DC power terminals...

Page 3: ...covers Safety cover s are used to cover potentially hazardous voltages Observe the following when removing safety cover s Switch off the unit Disconnect the unit from the mains supply or power outlet...

Page 4: ...als sicher angesehen werden wenn die minus DC Anschlussklemme des Ger ts im Verh ltnis zur Erdung 1000 VDC 707 Vpk nicht berschreitet f r SM70 CP 450 SM210 CP 150 und SM500 CP 90 oder 1500VDC 1060Vpk...

Page 5: ...ie Folgendes wenn Sie die Sicherheitsabdeckung en entfernen Ger t ausschalten Ger t von dem Versorgungsnetz oder der Stromquelle trennen Warten Sie 5 Minuten damit interne Kondensatoren sich entladen...

Page 6: ...er In the front menu go to SYSTEM INFO UNIT VERSION If an update is required refer to the SM15K unit manual how to do this 3 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs...

Page 7: ...first insert the bolts with crinkle washers in all DC power terminals Then assemble the entire strip to the DC power terminals This because bolts cannot be inserted in the DC power terminals once the...

Page 8: ...rip because it will burn out o Place the special M S parallel safety covers over the output terminals o Cover with marking DWG2532 is for the outputs of the upper and lower units Cover DWG2533 is for...

Page 9: ...own in the display see fig 3 6 The master or slave can also be configured via the web interface or using Ethernet commands After changing master or slave settings stored sequences need to be rebuilt d...

Page 10: ...how to do this 4 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs and Outputs or the Sense Connector when the SM15K unit is connected to the mains supply or power outlet Safe...

Page 11: ...N M o 6 Relay 1 NC o 5 Relay 1 NO o 4 Relay 1 Common o 3 Relay 2 NC o 2 Relay 2 NO o 1 Relay 2 Common Pinning CON N o 6 Relay 3 NC o 5 Relay 3 NO o 4 Relay 3 Common o 3 Relay 4 NC o 2 Relay 4 NO o 1 R...

Page 12: ...to the SM15K unit manual how to do this 5 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs and Outputs or the Sense Connector when the SM15K unit is connected to the mains su...

Page 13: ...e monitored Download the manual Ethernet Sequencer Programming SM15K for details 5 9 TROUBLE SHOOTING Check the programming source is set to the correct slot Check the output is switched ON the Interl...

Page 14: ...the unit must be in CC mode and when programming a power the unit must be in CP mode 5 10 CALIBRATION Calibration of the interface is not applicable 5 11 Settings Settings via the web page o Bus type...

Page 15: ...red refer to the SM15K unit manual how to do this 6 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs and Outputs or the Sense Connector when the SM15K unit is connected to th...

Page 16: ...pin 15 The user inputs have a working range of 2V 30V use a common zero and have an impedance of approximately 22kOhms The maximum load of the 5V is 100mA See figure 6 4 and table 6 1 for the pinning...

Page 17: ...mware package is P0120 or higher In the front menu go to SYSTEM INFO UNIT VERSION If an update is required refer to the SM15K unit manual how to do this 7 4 HARDWARE INSTALLATION Warning Never make co...

Page 18: ...afe value Note that the programming inputs are floating with regards the power output Turn the output on again with the OUTPUT ON OFF button To program the unit by current instead of voltage simply us...

Page 19: ...ble to use a relay contact or a switch to shut the unit down see fig 7 9 In standby mode the power supply consumes very little power Note also via Eth or other interfaces RSD can be activated 7 10 REF...

Reviews: