SAFETY INSTRUCTIONS 

 

SM15K INTERFACES 

2 / 19 

DELTA ELEKTRONIKA B.V. 

rev. Nov. 2019 

 

Warning!

 When the 'plus' DC power terminal can exceed 60VDC in respect to the 'minus' DC power terminal, 

additional external measures must be taken to ensure safety isolation of the DC power terminals and sense 
connections. 

Warning!

 When the 'minus' DC power terminal of the unit can exceed 60VDC / 42.4Vpk in respect to ground, 

additional external measures must be taken to ensure safety isolation of the DC power terminals and sense 
connections. 

The standard LAN, USB and Interlock connectors and optional interfaces are at ground level and can be considered 
safe if the 'minus' DC power terminal of the unit does not exceed 1000VDC / 707Vpk in respect to ground for  
SM70-CP-90, SM210-CP150 and SM500-CP-90, or does not exceed 1500VDC / 1060Vpk in respect to ground for 
SM1500-CP-30. 

1

 

SAFETY INSTRUCTIONS - SM15K-series 

1.1

 

Caution 

The following safety precautions must be observed during all phases of operation, service and repair of this equipment. 
Failure to comply with the safety precautions or warnings in this document violates safety standards of design, 
manufacture and intended use of this equipment and may impair the built-in protections. Delta Elektronika shall not be 
liable for user’s failure to comply with these requirements. 

1.2

 

Installation Category 

The Delta Elektronika power supplies have been evaluated to installation category II (Over voltage category II). 

1.3

 

Grounding of Mains Terminals (AC Power Terminals) 

This product is a safety Class 1 unit. To minimize shock hazard, the unit must be connected to the AC Power Supply 
mains through a four conductor power cable, with the ground wire firmly connected to an electrical ground (safety 
ground) at the power outlet. 
 
For units designed to be hard-wired to the mains supply, the protective earth terminal must be connected to the safety 
electrical ground before another connection is made. Any interruption of the protective ground conductor, or 
disconnection of the protective earth terminal will cause a potential shock hazard that might cause personal injury. 

1.4

 

Grounding of DC Power Terminals 

If the DC power terminal of a unit is specified to sink or source to a maximum of 60VDC, and either the 'minus' or 'plus'  
DC power terminal is grounded, the voltage on the DC power terminals and sense connections can be considered safe. 

Caution 1:

 If a low voltage unit has both DC power terminals floating, or if the terminals are in series with an external 

high AC or DC voltage, the 'minus' DC power terminal can exceed the safe value in respect to ground as specified in the 
above warning!  

Caution 2:

 Although a high voltage unit is set to a safe voltage below 60VDC, for safety it must always be considered as 

a high voltage unit!  Wrong operation, a programming error or an external defect can result in an unsafe high DC output  
voltage.  
 
For more information and schematics regards Grounding & Safety, see application note 

"Safe operation of a power 

supply"

 on the Delta Elektronika website. 

1.5

 

Danger of electrical shock 

Touching the contacts of the mains plug or wires directly after disconnecting from the mains, can cause an electrical 
shock. And there can still be a dangerous voltage between one of the DC power terminals and the PE because of 
charged X-capacitors. This can also happen when the DC power output is switched off, but the unit is still switched on! 
Therefore never touch PE and one of the DC power terminals at the same time. 

1.6

 

Connection to mains supply 

Either connect to the mains supply permanently or via an industrial type plug, complying with IEC 60309. 
"Permanently connected equipment" or "Pluggable equipment type B". 

1.7

 

Fuses 

Fuses must be changed by authorized Delta Elektronika service personnel only, for continued protection against risk of 
fire. 

1.8

 

AC Input Ratings 

Do not use an AC Supply which exceeds the AC input voltage and frequency rating of this unit. The AC input voltage and 
frequency rating of the Delta Elektronika power supply series are stated in the accompanying datasheet. 

1.9

 

Live Circuits 

Operating personnel should not remove the unit covers. No internal adjustment or component replacement is allowed by 
non Delta Elektronika qualified personnel. Never replace components with the power cable connected. To avoid injuries, 
always disconnect power, remove external voltage sources and discharge circuits before touching components. 

1.10

 

Parts Substitutions & Modifications 

Parts substitutions and modifications are allowed by authorized Delta Elektronika service personnel only. For repairs or 
modifications the unit must be returned to a Delta Elektronika service facility. 

Summary of Contents for SM15K Series

Page 1: ...on P0120 Contents 1 Safety Instructions 2 Sicherheitshinweise 3 Master Slave Interface 4 Isolated Contacts 5 Serial Interface 6 Digital User I O 7 Isolated Analog Interface Firmware Update It is stron...

Page 2: ...nd either the minus or plus DC power terminal is grounded the voltage on the DC power terminals and sense connections can be considered safe Caution 1 If a low voltage unit has both DC power terminals...

Page 3: ...covers Safety cover s are used to cover potentially hazardous voltages Observe the following when removing safety cover s Switch off the unit Disconnect the unit from the mains supply or power outlet...

Page 4: ...als sicher angesehen werden wenn die minus DC Anschlussklemme des Ger ts im Verh ltnis zur Erdung 1000 VDC 707 Vpk nicht berschreitet f r SM70 CP 450 SM210 CP 150 und SM500 CP 90 oder 1500VDC 1060Vpk...

Page 5: ...ie Folgendes wenn Sie die Sicherheitsabdeckung en entfernen Ger t ausschalten Ger t von dem Versorgungsnetz oder der Stromquelle trennen Warten Sie 5 Minuten damit interne Kondensatoren sich entladen...

Page 6: ...er In the front menu go to SYSTEM INFO UNIT VERSION If an update is required refer to the SM15K unit manual how to do this 3 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs...

Page 7: ...first insert the bolts with crinkle washers in all DC power terminals Then assemble the entire strip to the DC power terminals This because bolts cannot be inserted in the DC power terminals once the...

Page 8: ...rip because it will burn out o Place the special M S parallel safety covers over the output terminals o Cover with marking DWG2532 is for the outputs of the upper and lower units Cover DWG2533 is for...

Page 9: ...own in the display see fig 3 6 The master or slave can also be configured via the web interface or using Ethernet commands After changing master or slave settings stored sequences need to be rebuilt d...

Page 10: ...how to do this 4 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs and Outputs or the Sense Connector when the SM15K unit is connected to the mains supply or power outlet Safe...

Page 11: ...N M o 6 Relay 1 NC o 5 Relay 1 NO o 4 Relay 1 Common o 3 Relay 2 NC o 2 Relay 2 NO o 1 Relay 2 Common Pinning CON N o 6 Relay 3 NC o 5 Relay 3 NO o 4 Relay 3 Common o 3 Relay 4 NC o 2 Relay 4 NO o 1 R...

Page 12: ...to the SM15K unit manual how to do this 5 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs and Outputs or the Sense Connector when the SM15K unit is connected to the mains su...

Page 13: ...e monitored Download the manual Ethernet Sequencer Programming SM15K for details 5 9 TROUBLE SHOOTING Check the programming source is set to the correct slot Check the output is switched ON the Interl...

Page 14: ...the unit must be in CC mode and when programming a power the unit must be in CP mode 5 10 CALIBRATION Calibration of the interface is not applicable 5 11 Settings Settings via the web page o Bus type...

Page 15: ...red refer to the SM15K unit manual how to do this 6 4 HARDWARE INSTALLATION Warning Never make connections to the Power Inputs and Outputs or the Sense Connector when the SM15K unit is connected to th...

Page 16: ...pin 15 The user inputs have a working range of 2V 30V use a common zero and have an impedance of approximately 22kOhms The maximum load of the 5V is 100mA See figure 6 4 and table 6 1 for the pinning...

Page 17: ...mware package is P0120 or higher In the front menu go to SYSTEM INFO UNIT VERSION If an update is required refer to the SM15K unit manual how to do this 7 4 HARDWARE INSTALLATION Warning Never make co...

Page 18: ...afe value Note that the programming inputs are floating with regards the power output Turn the output on again with the OUTPUT ON OFF button To program the unit by current instead of voltage simply us...

Page 19: ...ble to use a relay contact or a switch to shut the unit down see fig 7 9 In standby mode the power supply consumes very little power Note also via Eth or other interfaces RSD can be activated 7 10 REF...