DeviceNet Slave Communication Card CMC-DN01
DVP-PLC Operation Manual
10
Figure 5.1.1: A constructed DeviceNet network
2. Setting DVPDNET-SL and VFD-C2000 series AC motor drive:
Module
Node address
Baud rate
DVPDNET-SL 1
500
kbps
VFD-C2000 series AC motor drive
2
500 kbps
Note: Setting the node address and baud rate of VFD-C2000 series AC motor drive in the DeviceNet
network is shown below.
Parameter
Explanation
Setting range
P00-20
The source of the
frequency instruction
8
P00-21
The source of the running
instruction
5
P09-30
Communication decoding
method
0
P9-70
The node address of the
AC motor drive in the
DeviceNet
DeviceNet: 0-63
Standard mode
Extended mode
P9-71
The baud rate of the AC
motor drive in the
DeviceNet
0: 125 Kbps
1: 250 Kbps
2: 500 Kbps
0: 10 Kbps
1: 20 Kbps
2: 50 Kbps
3: 125 Kbps
4: 250 Kbps
5: 500 Kbps
6: 800 Kbps
7: 1 Mbps