DeviceNet Slave Communication Card CMC-DN01
DVP-PLC Operation Manual
17
DVPDNET-SL. If DVP-SV PLC is in RUN status during the download, a warning dialog box
will appear.
4. Click “OK” to download the configuration to DVPDNET-SL and make sure the PLC is in
RUN status. You will then see the MS LED and NS LED on CMC-DN01 are on in green
color.
5.3 Data
Mapping
After you configure the DeviceNet network following the steps above, you will then get the data
mapping relations as below.
DVPDNET-SL
VFD-C2000 series AC motor
drive
D6287 H2000
D6288
H2001
D6037 H2101
D6038
H2103
5.4 Editing Ladder Diagrams in PLC
I/O data contain the control word, status word, given frequency and output frequency of the AC motor
drive, and therefore we manage to control the run/stop, forward running, reverse running and running
speed of VFD-C2000 by a ladder diagram. See the example of a ladder diagram below.
When X0 = ON, C2000 forward running is enabled.
When X0 = ON, C2000 running frequency is 30Hz.
When X1 = ON, C2000 stops running.
C2000 output frequency is stored in D0.
6 Error Codes on Key Pad
When errors occur in the communication between CMC-DN01 and VFD-C2000 series AC motor
drive, the error codes will be displayed on the digital key pad.
Error code
Indication
How to correct
ECid
CMC-DN01 duplicate MAC
ID detection error; incorrect
Modify the value for parameter P09-70 in the AC
motor drive and re-power it.