DeviceNet Slave Communication Card CMC-DN01
DVP-PLC Operation Manual
5
3 Basic
Operation
3.1 Installation
How to install
①
Use an efficient tool to peel the communication cable
for approx. 30mm. DO NOT damage the shielded
cable during the peeling.
Approx. 30mm
②
Peel off the metallic shielded net and foil, and you will
see 2 power cables (red and black), 2 signal cables
(blue and white) and 1 shielded cable.
Shielded cable
③
Peel off the exterior metallic shielded net, foil and the
plastic cover of the power cable and signal cable in
proper length.
④
Insert the peeled communication cables into the holes
in the connector in correct order.
Black (V-)
Blue (CAN_L)
Shielded cable (CAN_SHLD)
Red (V+)
White (CAN_H)
⑤
Tighten the screws on the connector by a slotted
screwdriver and fix the communication cables in the
holes in the connector.
Screw by a slotted
screwdriver
⑥
Install CMC-DN01 on the VFD-C2000 series AC motor drive:
1. Switch off the power supply of VFD-C2000.
2. Open the cover on top of VFD-C2000.
3. Place the insulation spacer into the positioning pin and aim the two holes on the PCB at the
positioning pin. Press the pin to clip the holes with the PCB (Figure 1).
4. Screw up after the PCB is clipped with the holes (Figure 2).
[Figure 1]
[Figure 2]
⑦
Connect to the DeviceNet port: Insert the DeviceNet connector to the DeviceNet port on CMC-DN01
(Figure 3).