Chapter 5 Trial Run and Tuning Procedure
|
ASDA-B Series
5-12
Revision January 2009
Tuning Procedure
13. Pressing UP key is forward rotation and pressing DOWN key is reverse rotation.
14. Execute JOG operation in low speed first. After the machine is running smoothly, then execute JOG
operation in high speed.
15. The ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor) cannot be shown in the display of
JOG parameter P4-05 operation. Please press MODE key twice continuously and the users can see
the ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor). Then, execute JOG operation again,
press MODE key once and press SET key twice to view the display on the keypad. Check if the value
of J_load /J_motor is adjusted to a fixed value and displayed on the keypad after acceleration and
deceleration repeatedly.
ASD-PU-01B
Estimate the ratio of Load Inertia to Servo Motor Inertia (J_load /J_motor): JOG Mode
Tuning Procedure
Display Message
1. After wiring is completed, when power in connected to the AC servo
drive, the right side display will show on the LED display.
2. Press MODE key to enter into parameter mode.
3. Press SHIFT key twice to select parameter group.
4. Press UP key to view each parameter and select parameter P2-13.
5. Use UP and DOWN key to cycle through the available settings.
Then, press SET key to set the setting value of parameter P2-13 as
shown on the right side display (Set DI Enabled Status to “Normally
open” status).
6. Repeat the action of 4 and 5. Set the setting value of parameter P2-
14 as shown on the right side display.
7. Repeat the action of 4 and 5. Set the setting value of parameter P2-
15 as shown on the right side display.
8. Press MODE key to enter into Monitor mode.
9. Press DOWN key twice to select the ratio of Load Inertia to Servo
Motor Inertia (J_load /J_motor).
10. Press FUNC key on the keypad to enter into JOG mode, and the
right side display will show on the LED display
11. The default JOG speed value is 20rpm. The users can press UP and
DOWN key to increase and decrease JOG speed. Press SHIFT key
one time can add one digit number. Adjust JOG speed as 200rpm
shown on the right side display.
12. After select desired JOG speed, press SET key and the right side
display show on the LCD display.
Summary of Contents for ASD-B0121-A
Page 1: ......
Page 13: ...Table of Contents ASDA B Series Revision January 2009 This page intentionally left blank...
Page 72: ...Chapter 4 Display and Operation ASDA B Series Revision January 2009 4 17 Figure 4 7...
Page 75: ...Chapter 4 Display and Operation ASDA B Series 4 20 Revision January 2009 Figure 4 9...
Page 77: ...Chapter 4 Display and Operation ASDA B Series 4 22 Revision January 2009 Figure 4 10...
Page 79: ...Chapter 4 Display and Operation ASDA B Series 4 24 Revision January 2009 Figure 4 11...
Page 92: ...Chapter 4 Display and Operation ASDA B Series Revision January 2009 4 37 Figure 4 21...
Page 291: ...Chapter 12 Application Examples ASDA B Series 12 2 Revision January 2009 PLC Program...
Page 292: ...Chapter 12 Application Examples ASDA B Series Revision January 2009 12 3...
Page 293: ...Chapter 12 Application Examples ASDA B Series 12 4 Revision January 2009...
Page 297: ...Chapter 12 Application Examples ASDA B Series 12 8 Revision January 2009 Position Control 1...
Page 298: ...Chapter 12 Application Examples ASDA B Series Revision January 2009 12 9 Position Control 2...
Page 299: ...Chapter 12 Application Examples ASDA B Series 12 10 Revision January 2009 JOG Operation...
Page 302: ...Chapter 12 Application Examples ASDA B Series Revision January 2009 12 13...