Table 4. Slot assignments
Description
Slot
QLogic, 41164 4 Port, 10GbE SFP+ PCIe, Full Height
5, 8, 1
QLogic, 41164 4 Port, 10GBASE-T PCIe, Full Height
5, 8, 1
QLogic, 41164 4 Port, 10GBASE-T PCIe, Low Profile
6
QLogic, 41262 2 Port, 25Gb SFP28 PCIe, Full Height
5, 8, 1
QLogic, 41262 2 Port, 25Gb SFP28 PCIe, Low Profile
6
HBA330 SAS Controller, 12Gbps Mini card
mini/mono
QAT,INTEL,8970,FH, Avnet p/n 1QA89701G1P5
4
PM8072,SAS12,4P,FH, MicroSemi 2295200-R
3, 7, 5
FC16,QLE2694-DEL-BK,TRG,QP,FH
5, 8, 1
16GB NVRAM,FH
2
2. Enter the
enclosure show io-cards
command to check the status of each I/O. Record the failed I/O. A sample output
is shown.
Shut down and disconnect the system
Prerequisites
Establish a connection to the system as described in
Establish a serial management connection to the PowerProtect system
page 14.
About this task
Complete the following steps to shut down and disconnect the system.
Steps
1. Stop the system using the
system poweroff
command to allow the proper shut down of the file system and other system
components. The power down process takes approximately five minutes to complete. The
system poweroff
command
immediately turns the front panel blue LED to amber, and is complete when the front panel LED turns off.
NOTE:
The system fans still run, and NIC port LEDs still flash after running the
system poweroff
command.
2. Open the cable management arms.
3. Label each of the cables as to their connection location. Taking a photograph for reference is also helpful for re-connecting
the cables.
4. Disconnect the AC power cords from the rear of the system.
5. Disconnect all network cables from the rear of the system.
6. Disconnect all SAS cables from the rear of the system.
7. Disconnect the serial console cable.
58
Replace a PCIe HBA (SAS, FC, or NIC)