Key
Description
Minimum distance (in / cm)
G
Distance between the rear-facing surface of the PDU and the surface of the rack
post. This space must be large enough to house power cables and route customer
host cables.
3 / 7.7
H
PDU depth from rack sidewall.
I
If a front door exists, this is the distance between the back surface of the door and
the front surface of the vertical NEMA rail. Space is required to provide clearing for
bezel airflow.
2.5 / 6.4
J
Space required for enclosures, rails, and cable management arms.
37 / 94
K
PDU width.
L
Distance from the equipment enclosure area to the front-facing side of the PDU.
0.1 / 0.26
M
AC cable bend radius. The bend radius is expected to encroach into the equipment
enclosure area.
4 / 10.2
54
Third Party Racking Option for PowerMax 2000