Height 75.0 in.
(190 cm)
Depth 39.37 in.
(100 cm)
(not including bezels)
Width 24.0 in.
(61 cm)
Rear Access
(76 cm)
30.00 in.
Front Access
(106 cm)
42 in.
Figure 4. Cabinet dimensions and clearances
Tile placement
You must understand tile placement to ensure that the array is positioned properly and to allow sufficient room for service and cable
management.
When placing the array, consider the following:
•
Typical floor tiles are 24 in. (61 cm) by 24 in. (61 cm).
•
Typical cutouts are:
○
8 in. (20.3 cm) by 6 in. (15.2 cm) maximum.
○
9 in. (22.9 cm) from the front and rear of the floor tile.
○
Centered on the tiles, 9 in (22.9 cm) from the front and rear and 8 in (20.3) from sides.
•
Service area of 42 in (106 cm) for the front and 30 in (76 cm) for the rear on the system bays.
The following figure provides tile placement information for all PowerMax 2000 arrays.
26
Position PowerMax 2000 Bay