Delem
V0614, 3.8
With this option the analogue outputs can be tested. These signals are used for the control
amplifiers of the X-axis and auxiliary axes. The output voltage varies between -10V and
+10V. The value (+/- 255 DA-points) can be altered with the manual movement keys.
The string ‘OUTAN1’ and ‘OUTAN2’ refer to the outputs in the analog A connector. See the
schematic 8063-104 for the location of these outputs.
•
Output test and adjustment procedure
1. Set both the OUTAN1 and the OFFAN1 to zero by using the manual movement keys.
Meaning that you should measure 0V at the output and the connected axis should not
move.
2. If the measured output voltage is not zero, you must set the output voltage to zero with
the OFFAN1 adjustment.
3. With the zero output voltage the motor should not move. A possible movement can be
corrected with the offset adjustment of the concerning motor drive.
4. For further fine-tuning you can adjust the value of the OFFAN1 again.
•
Testing the digital inputs
In case a digital input is active, the indication on the screen will be ‘1’, otherwise the
indication is ‘0’. When you connect a DC-voltage of 24V at the selected input, the signal
indication of the corresponding input on the screen must become ‘1’.
If none of the inputs is working, please check the common input connection and the general
+24V.
•
Testing the digital outputs
Move with the cursor keys to a digital output number, Press ‘1’ to activate the output. In case
you press ‘0’ the output is deactivated.
•
Testing the analogue inputs
The value on the screen is the read-out of the voltage in DA-points which is offered to the
analogue input. By varying the voltage the read-out should vary likewise.
Failure
External electronics, DA-52s or the wiring (including connectors).