2.5. Control Rescue procedure
The Rescue procedure for the Delem control is meant to re-install all original software on the
control. It is meant as a last resort, when other attempts to ‘cure’ the control have failed
and/or the control does no longer boot from the internal flash memory).
When this procedure is carried out, all existing data on the hard drive is erased: products,
tools, etc. This also means that license codes for control options are erased. These options
can be requested again with the original vouchers.
This procedure can only be successful when all hardware is still functional.
Following two situations have different approaches for the rescue operation:
-
What to do when the DA-52s application does not start?
(The control boots and shows the desktop)
-
What to do when the Control does not boot?
(The display shows a black screen with a Delem logo)
What to do when the DA-52s application does not start?
(The control boots and shows the desktop)
Preparation
To perform the procedure on the control the following is necessary:
- USB-stick with a backup or update software
Procedure
1. Switch off the power of the control
2. Press and hold the
- key
3. Switch on the power
The following message will appear:
4. Enter the access code: 25789 followed by the enter-key
The following message will appear:
5. Select option: 1
6. Follow the instructions on the screen (here you need the USB-stick with backup- or
update software).