Installation guide
DEiMiC ONE MASTER v1.8
2.2.3. CONNECTIONS INSIDE ELECTRICAL SWITCHGEAR
1. Every building outgoing wire, which are not controlled by the
DEiMiC system
(electric sockets, furnace, alarm, fridge power supplies etc.) should be
connected to circuits breakers like in traditional installations.
2. Circuits controlled by
DEiMiC system should be connected according to
following rules:
a) Neutral wires connected on terminal strips comply with residual-current
devices.
b) Ground wires connected to grounded strips.
c)
Lighting hot wires led out at single terminal.
d)
Shutters hot wires led out at two single terminal, where first one sets
the
direction up (apply the same rule for roof windows and other mechanisms
where direction is controlled by wire connection sequence), second one – the
direction down.
e)
Switchable electric sockets hot wires led out at single terminal.
f)
Switches UTP cables led to an electrical switchgear with description
and
enough free space to allow access for every place in the switchgear.
g) Sensors UTP cables led to an electrical switchgear with description and
enough free space to allow access for every place in the switchgear.
h) Temperature sensors cables led to an electrical switchgear with description
and enough free space to allow access for every place in the switchgear
.