31
Installation guide
DEiMiC ONE MASTER v1.8
5.3. CENTRAL HEATING
Following text includes information about requirements which have to be met
to ensure the system control capability of heating and DHW circulation pump.
Heating are controlled by the DEiMiC system via closing heat supply valves.
The temperature sensors should be installed in the chosen rooms.
Their measurements will be the base of zoning heating control, thereby there
is no need to mount additional controllers inside rooms.
The heating system can be based on any heat supply and we not interfere in
the furnace automation system, which only task is to maintain the given
temperature setpoint.
In rooms with regulated temperature, heat supply should be limited with
NO 230 V actuator (normally open).
To ensure proper assembly process, please follow the rules below:
1. Heat distributors location should be shown to an electrician, which should be
informed about number of heating zones per single distributor, so he will be
able to prepare wiring.
2. Installer must deliver and mount actuators in every place, where it is needed
(the distributors, radiators and other necessary places).
3. An electrician should be informed about a need to route 2x1mm
2
wire to
every actuator (hot and neutral wires).
If actuator needs another connection, the installer and the investor should
be informed immediately.