SPECIAL FUNCTIONS - MENU 1 

 
It is possible to activate special functions that vary the operation of the two relay outputs and other functions such 
as: the deactivation of network failure signal on the relay, deactivate the liquid control, activate a relay during firing, 
deactivation of the burner washing cycle, "Bistable" shot mood, burner preheating (it is maintained at 50% of the 
operating temperature during the disarming, this to speed up the resetting phase). 
 
To access the "Menu 1" of Programming special functions you need: 
1. Disconnect ARM and FOG 
2. Note down the DIP-SWITCH configuration 
3. Turn all DIP-SWITCH OFF 
4. Remove the Jumper from BUZZ (J3) 
5. Place the Jumper on J2 
6. Set all DIP-SWITCHS to ON for the functions to be activated 
7. Remove the Jumper from J2 and replace it on BUZZ (J3) 
8. Restore the DIP-SWITCH as noted down before (point 2) 

 

DIP-SWITCH 

FUNCTIONING 

 

SPECIAL FUNCTIONS PROGRAMMING (J2 CLOSED) 

 

 

DIP1  DIP2  DIP3  DIP4  DIP5  DIP6  DIP7  DIP8 

DIP9 

SETTING 

LACK OF 

NETWORK 

SIGNALING 

OFF 

OFF 

LACK OF NETWORK SIGNALED ON 

STATE RELAY 

ON 

ON 

LACK OF NETWORK NON-SIGNALED 

ON STATE RELAY 

 

LIQUID LEVEL 

CONTROL

 

OFF 

OFF 

LIQUID LEVEL CONTROL ACTIVATED 

(standard) 

ON 

ON 

LIQUIDI LEVEL CONTROL 

DEACTIVATED 

STATE RELAY 

LOGIC 

 

 

OFF 

OFF 

RELE N.O.; 

CLOSED IF ARMED 

WITHOUT ALARMS 

ON 

ON 

RELE N.O.; 

CLOSED IF IN ALARM 

 

LIQUID LEVEL 

LOGIC

 

OFF 

OFF 

RELE N.C.; 

IT IS OPEN WHEN THERE 

IS A LACK OF LIQUID (standard) 

ON 

ON 

RELE NO.; 

IT IS CLOSED WHEN 

THERE IS A LACK OF LIQUID 

 

LIQUID/SHOT 

RELAY

 

OFF 

OFF 

RELAY USED AS LACK OF LIQUID 

(standard) 

ON 

ON 

RELE N.O.; 

CLOSES WHEN 

SHOOTING 

SAVE PUMP 

OFF 

OFF 

SAVE PUMP FUNCTION DISABLED 

ON 

ON 

SAVE PUMP FUNCTION ENABLED 

DO NOT WASH 

OFF 

OFF 

WASH IF PROVIDED 

ON 

ON 

WASH AUTOMATICALLY EXCLUDED 

 

BIESTABLE SHOT 

 

OFF 

OFF 

IMPULSE SHOT INPUT 

 

ON 

ON 

BIESTABLE SHOT INPUT 

 

HEATING 

PREHEATING 

OFF 

OFF 

PREHEATING FUNCTION DISABLED 

 

ON 

ON 

PREHEATING FUNCTION ENABLED 

 

 

 

Summary of Contents for DT-800Lan

Page 1: ...Manual of installation and maintenance Fog Generators DEFENDERTECHDT 800Lan...

Page 2: ......

Page 3: ...e power supply of the appliance must be supplied through a special switch or plug in order to allow it to be switched off Danger of burns the components of the appliance are subject to heating do not...

Page 4: ...ct then this will have to report their presence to the Producer on penalty of forfeiture within one week of discovery 4 The Customer provided that he has provided a timely description of the data cont...

Page 5: ...igation to display The legislation provides for the obligation to post in the access route of the premises a notice that signals the presence of a Fog Generator Use the adhesive label supplied with th...

Page 6: ...adjustable up to 200 mm Nozzles extension lengh adjustable up to 500 mm Fog jet diversion kit passes through the wall behind the equipment Fog jet split and diversion kit 50 passes through the wall be...

Page 7: ...THE APPLIANCE Use 4 10 mm dowels fisher of the type suitable for the wall on which the machine will be installed If necessary it is possible to drill the bracket at any point of it adjacent to the wa...

Page 8: ...2 Place the appliance on the front of the bracket and let the four fins of the bracket penetrate the side slits of the appliance operation 1 3 Slide the appliance down 2nd operation 4 Using a 4mm Alle...

Page 9: ...Description DT 800Lan Control Card...

Page 10: ...te This contact can be used to assign other functions see p 14 special features STATE system status failure signal When the appliance is disarmed or switched off the Clean NA contact normally open wil...

Page 11: ...ording to the times programmed through the DipSwitch as shown in the table on page 13 If desired it is possible to change the contact activation mode to OPEN by turning ON the DipSwitch nr 3 Also ARM...

Page 12: ...vating this function the Fog2 input takes on the task of preventing accidental firing If a negative signal is present on FOG2 the shot will not be allowed If the signal arrives while the shot is in pr...

Page 13: ...X X X PUMP MODE CONTINUE X X X X X X X OFF X X IMPULSIVE DOUBLE THE SHOT TIME X X X X X X X ON X X RESISTANCE NUMBER 1 X X X X X X X X OFF OFF 2 X X X X X X X X ON OFF X X X X X X X X X X X X X X X X...

Page 14: ...ORK SIGNALING OFF OFF X X X X X X X X LACK OF NETWORK SIGNALED ON STATE RELAY ON ON X X X X X X X X LACK OF NETWORK NON SIGNALED ON STATE RELAY LIQUID LEVEL CONTROL OFF X OFF X X X X X X X LIQUID LEVE...

Page 15: ...nctions of the Menus 1 and 2 you will have to program them simultaneously starting from those of the menu 1 activate the DIP10 and then the DIP corresponding to the desired functions of the Menu2 DIP...

Page 16: ...PAUSE STATE FIXED ON THE APPLIANCE IS IN THE FORCED PAUSE STATE it will ignore every firing commands untili its end ONE FLASH FOR EVERY RIARMAMENT OF THE MACHINE FAILURE LED6 RED TURNED OFF NO ALLARM...

Page 17: ...on peaks especially if there are more Fogs Generators or there is only one that is turned on 24H SHOT MANAGEMENT The shot is inhibited when the appliance is unarmed the burner temperature is lower tha...

Page 18: ...DT MultiFogControl is responsible for monitoring simultaneously the operating status of several Fogs Generators even in different geographical sites Both software can be requested free of charge by m...

Page 19: ...s incorrect reset the error by operating the DipSwitch no 5 if it persists the appliance will not work until it is replaced by the service DefenderTech LACK_NETWORK_ALARM self restoring lack of electr...

Page 20: ...re the liquid level to the 100 acting on DipSwitch nr 4 TECHNICAL INSTALLATION Once the machine is connected to the mains activate the buffer battery connecting the flying cable to the respective free...

Page 21: ...following is prescribed to Replace the buffer batteries 2x12V 1 3 are wired in series Arm the appliance by measuring voltage and absorption on the 230V mains Perform a full 60 second shot using water...

Page 22: ...1 DT 1600plus Lan 1601 DefenderTech Fog Generator Device Fog Genrator for safety applications They comply with the European Community Directives Low Voltage 2004 108 CE Electromagnetic Compatibily 200...

Page 23: ...ion directive C E E HAZARD IDENTIFICATIONS No specific danger can be found in the use of the effects PHYSICAL AND CHEMICAL PROPERTIES Physical state liquid Appearance and color liquid of transparent c...

Page 24: ...www defendertech eu info defendertech eu Tel 39 0721 1626113 Fax 39 0721 0731145...

Reviews: