SPECIAL FUNCTIONS - MENU 1
It is possible to activate special functions that vary the operation of the two relay outputs and other functions such
as: the deactivation of network failure signal on the relay, deactivate the liquid control, activate a relay during firing,
deactivation of the burner washing cycle, "Bistable" shot mood, burner preheating (it is maintained at 50% of the
operating temperature during the disarming, this to speed up the resetting phase).
To access the "Menu 1" of Programming special functions you need:
1. Disconnect ARM and FOG
2. Note down the DIP-SWITCH configuration
3. Turn all DIP-SWITCH OFF
4. Remove the Jumper from BUZZ (J3)
5. Place the Jumper on J2
6. Set all DIP-SWITCHS to ON for the functions to be activated
7. Remove the Jumper from J2 and replace it on BUZZ (J3)
8. Restore the DIP-SWITCH as noted down before (point 2)
DIP-SWITCH
FUNCTIONING
SPECIAL FUNCTIONS PROGRAMMING (J2 CLOSED)
DIP1 DIP2 DIP3 DIP4 DIP5 DIP6 DIP7 DIP8
DIP9
SETTING
LACK OF
NETWORK
SIGNALING
OFF
OFF
X
X
X
X
X
X
X
X
LACK OF NETWORK SIGNALED ON
STATE RELAY
ON
ON
X
X
X
X
X
X
X
X
LACK OF NETWORK NON-SIGNALED
ON STATE RELAY
LIQUID LEVEL
CONTROL
OFF
X
OFF
X
X
X
X
X
X
X
LIQUID LEVEL CONTROL ACTIVATED
(standard)
ON
X
ON
X
X
X
X
X
X
X
LIQUIDI LEVEL CONTROL
DEACTIVATED
STATE RELAY
LOGIC
OFF
X
X
OFF
X
X
X
X
X
X
RELE N.O.;
CLOSED IF ARMED
WITHOUT ALARMS
ON
X
X
ON
X
X
X
X
X
X
RELE N.O.;
CLOSED IF IN ALARM
LIQUID LEVEL
LOGIC
OFF
X
X
X
OFF
X
X
X
X
X
RELE N.C.;
IT IS OPEN WHEN THERE
IS A LACK OF LIQUID (standard)
ON
X
X
X
ON
X
X
X
X
X
RELE NO.;
IT IS CLOSED WHEN
THERE IS A LACK OF LIQUID
LIQUID/SHOT
RELAY
OFF
X
X
X
X
OFF
X
X
X
X
RELAY USED AS LACK OF LIQUID
(standard)
ON
X
X
X
X
ON
X
X
X
X
RELE N.O.;
CLOSES WHEN
SHOOTING
SAVE PUMP
OFF
X
X
X
X
X
OFF
X
X
X
SAVE PUMP FUNCTION DISABLED
ON
X
X
X
X
X
ON
X
X
X
SAVE PUMP FUNCTION ENABLED
DO NOT WASH
OFF
X
X
X
X
X
X
OFF
X
X
WASH IF PROVIDED
ON
X
X
X
X
X
X
ON
X
X
WASH AUTOMATICALLY EXCLUDED
BIESTABLE SHOT
OFF
X
X
X
X
X
X
X
OFF
X
IMPULSE SHOT INPUT
ON
X
X
X
X
X
X
X
ON
X
BIESTABLE SHOT INPUT
HEATING
PREHEATING
OFF
X
X
X
X
X
X
X
X
OFF
PREHEATING FUNCTION DISABLED
ON
X
X
X
X
X
X
X
X
ON
PREHEATING FUNCTION ENABLED