![DeDietrich Innovens MCA 25/28 BIC Installation And Service Manual Download Page 66](http://html1.mh-extra.com/html/dedietrich/innovens-mca-25-28-bic/innovens-mca-25-28-bic_installation-and-service-manual_2462465066.webp)
n
Heating curve with BCT
The
BCT
(Base heat Curve Temperature) parameter allows a
minimum operating temperature to be imposed on the heating circuit
(this temperature may be constant if the circuit gradient is nil).
A
Maximum temperature of the circuit
Z
Water temperature in the circuit for an outside
temperature of 0°C
E
DAY
set point on the circuit
R
Outside temperature for which the maximum water
temperature in the circuit is reached
T
Value of the heating curve
Select the parameter
CIRC. CURVE ...
x
Value set to the parameter
HCZP D
When you modify the heating curve,
Z
and
R
are
recalculated and repositioned automatically.
5.5.5.
Finalizing work
1. Remove the measuring equipment.
2. Put the flue gas sampling plug back in place.
3. Refit the front panel. Tighten the two screws by a quarter turn.
4. Raise the temperature in the heating system to approximately
70°C.
5. Shut down the boiler.
6. After about 10 minutes, vent the air in the heating system.
7. Checking the hydraulic pressure. If necessary, top up the water
level in the heating system (recommended hydraulic pressure
between 1,5 and 2 bar).
8. Tick the gas category used on the data plate.
9. Complete the checklist.
10.Explain the operation of the installation, the boiler and the
regulator to the users.
11.Inform the user of the periodicity of maintenance work to be carried
out. Input the service date and the contact details of the installer.
¼
See chapter: "Customising maintenance", page 82.
12.Give all the instruction manuals to the user.
Commissioning of the boiler is now complete.
The various boiler parameters are preset in the factory.
These factory settings are suitable for the most common
heating systems. For other systems and situations, the
parameters can be modified.
20
0
-15
64
50
75
C°
C°
0.7
C002320-B
1
2
X
3
4
5
T001522-A
5. Commissioning
MCA 25/28 BIC
64
15/06/12 - 300022159-001-01
Summary of Contents for Innovens MCA 25/28 BIC
Page 7: ...15 06 12 300022159 001 01 5 ...
Page 122: ...9 Spare parts MCA 25 28 BIC 120 15 06 12 300022159 001 01 ...
Page 123: ......