Installer level - #SYSTEM menu
Parameter
Adjustment range Description
Factory setting Customer
setting
I.TEL:
(1)
ANTIFR
Start anti-freeze in boiler command
ANTIFR
0/1 A
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit A
0/1 B
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit B
0/1 A+B
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit A+B
0/1 C
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit C
0/1 A+C
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit A+C
0/1 B+C
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit B+C
0/1 A+B+C
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit A+B+C
0/1 DHW
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit ECS
0/1 A+DHW
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit A+ECS
0/1 B+DHW
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit B+ECS
0/1 A+B+DHW
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit A+B+ECS
0/1 C+DHW
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit C+ECS
0/1 A+C+DHW
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit A+C+ECS
0/1 B+C+DHW
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit B+C+ECS
0/1 AUX
ON or OFF contact:
I.TEL:
can be used as an
antifreeze activation inlet on circuit AUX (
S.AUX:
if the
AD249 option is connected or the parameter
O.PUMP
A
is set to
CIRC.AUX
)
When
I.TEL:
is not active, the auxiliary circuit (AUX)
follows the maximum boiler temperature (parameter
BOILER MAX
).
(1) The parameter is only displayed if
INSTALLATION
is set to
EXTENDED
(2) If the pump incorporated in the boiler is used for circuit A (parameter
CIRC. A:
set to
DIRECT
), the
M
A outlet is free
(3) The parameter is only displayed if the parameter
O.PUMP A
is set to
CIRC.AUX
or the 3-way valve PCB option is connected
MCA 25/28 BIC
5. Commissioning
15/06/12 - 300022159-001-01
59