4.8
Flue gas system connections
4.8.1.
Classification
9
4
2
2
2
4
4
3
6
8
5
5
5
7
7
7
C33(x)
C33(x)
C43(x)
C83(x)
C43(x)
C43(x)
C13(x)
C53
C83(x)
C83(x)
C33(x)
B23P
B23P
C93(x)
C93(x)
1
1
B33
B33
C002339-C
1
Configuration B
33
Connection to a collective pipe via a concentric pipe
(combustive air taken from the boiler room)
All of the pressurised parts of the appliance are
surrounded by air.
2
Configuration B
23
- B
23P
Connection to a chimney using a connection kit
(combustive air taken from the boiler room)
3
Configuration C
13(x)
Air/flue gas connection by means of concentric pipes to a
horizontal terminal (so-called forced flue)
4
Configuration C
33(x)
Air/flue gas connection by means of concentric pipes to a
vertical terminal (roof outlet)
5
Configuration C
43(x)
Air/flue gas connection to a collective conduit for
watertight boilers (3CE P system)
6
Configuration C
53
Air and flue gas connection separated by means of a bi-
flow adapter and single pipes (combustive air taken from
outside)
7
Configuration C
83(x)
Flue gas connection to a collective conduit for sealed
boilers. The air supply is individual via a terminal coming
from outside the building.
4. Installation
MCA 25/28 BIC
24
15/06/12 - 300022159-001-01