4.10.5.
Connecting a direct heating circuit
C002304-M
2
3
On/off
OT
BL
RL
Tout
Tdhw
1
TS +
B
A
B
0-10V
S AMB C
4 3 2 1
2 1
+ -
S AMB B
2 1
S AMB A
2 1
S SYST + TA -
S ECS
S EXT
S DEP C
2 1
2 1
2 1
2 1
2 1
S DEP B
2 1
SCU
PCU
4
A
Do not connect anything to the terminal block.
Z
Connect the outside temperature sensor.
E
Connect a safety thermostat if the heating circuit is for
underfloor heating.
4
Remove the bridge.
4
Connect the wires from the safety thermostat to the
connector.
R
Do not connect anything to the terminal block.
Settings to be made for this type of installation
Parameters
Access
Settings to be made See chapter
INSTALLATION
Installer level
#SYSTEM
menu
EXTENDED
¼
If safety thermostat is connected to
BL
on the connection terminal
block:
IN.BL
Installer level
#PRIMARY INSTAL.P
menu
STOP HEAT
¼
MCA 25/28 BIC
4. Installation
15/06/12 - 300022159-001-01
33