Name
Description
Factory
value
Minimum
Maximum Level
AP073
Average external temperature [°C] when switching
from summer/winter mode (with outside sensor)
22
10
30
User
AP074
Force summer mode (with outdoor sensor). Sanitary
(DHW) enabled and heating disabled.
0: Auto according to AP073
1: Summer
0
–
–
User
AP079
Building insulation level (with outside sensor)
0: Poorly insulated building
15: Well insulated building
3
0
15
Installer
AP080
External temperature [°C] below that at which anti-
frost protection is activated
-10
-30
+25
Installer
AP082
Not used
0
–
–
Installer
AP091
Type of outdoor sensor used:
0: Auto
1: Wired sensor
2: Wireless sensor
3: Internet measured
4: None
0
–
–
Installer
AP098
Configuration of boiler blocking input contact X15 (al
so see setting AP001)
0: Normally open
1: Normally closed
1
0
1
Installer
CP000
Max. settable heating setpoint temperature [°C]
80
25
80
Installer
CP020
Zone function
0: Disabled
1: Enabled
1
–
–
Installer
CP210
Comfort mode heating curve offset (with outside sen
sor)
15
15
90
Installer
CP230
Heating curve slope (with outside sensor)
1.5
0
4
Installer
CP470
Number of days required for the screed drying pro
gram
0
0
30
Installer
CP480
Screed drying starting temperature [°C]
20
20
50
Installer
CP490
Screed drying stop temperature [°C]
20
20
50
Installer
CP780
Zone control strategy selection
0: Automatic
1: Room Temp. based
2: Outdoor Temp. based
3: Outdoor & room based
0
–
–
Installer
DP003
Maximum fan speed in domestic hot water mode
[rpm]
See chapter
"Service Set
tings"
–
–
Installer
DP004
Anti-legionella function
0: Disabled
1: Weekly
2: Daily (only available with Room Unit)
0
–
–
User
DP005
Difference between the flow temperature and the
temperature requested by the calorifier tank [°C]
15
0
25
Installer
DP006
Difference between the temperature detected by the
calorifier tank sensor and the desired DHW tempera
ture that enables a heat request [°C]
4
2
15
Installer
DP007
Position of three-way valve in standby
0: CH operation
1: DHW (Domestic Hot Water)
1
–
–
Installer
DP034
Corrects in a negative sense the value measured by
the calorifier tank sensor [°C]
0
0
10
Installer
9 Settings
en
7804841 - 02 - 20012022
INIDENS
189
Summary of Contents for INIDENS 20/24 MI
Page 5: ...1 2 3 4 5 1 2 3 4 1 2 3 mm EN 60335 1 0 8 1 5 2 1 bg 7804841 02 20012022 INIDENS 5...
Page 6: ...De Dietrich 1 3 1 3 1 1 3 2 1 3 3 2 2 1 2 2 bg 2 6 INIDENS 7804841 02 20012022...
Page 24: ...13 BO 0000071 5 1 2 3 4 LIFT 10 6 7 8 9 b a LIFT 6 6 1 6 2 bg 6 24 INIDENS 7804841 02 20012022...
Page 26: ...16 BO 0000279 40 6 3 30 Nm 6 3 1 6 3 2 1 2 1 2 bg 6 26 INIDENS 7804841 02 20012022...
Page 42: ...7 7 1 28 7 2 1 2 3 4 5 1 0 1 5 6 7 8 9 7 3 60 mbar 6 kPa bg 7 42 INIDENS 7804841 02 20012022...
Page 72: ...1 2 3 4 5 6 7 8 9 10 bg 13 72 INIDENS 7804841 02 20012022...
Page 76: ...1 2 3 4 5 1 2 3 4 1 2 3 mm EN 60335 1 0 8 bar 1 5 2 bar el 1 76 INIDENS 7804841 02 20012022...
Page 77: ...De Dietrich 1 3 1 3 1 1 3 2 1 3 3 2 2 1 2 2 2 el 7804841 02 20012022 INIDENS 77...
Page 95: ...59 BO 0000071 5 1 2 3 4 LIFT 10 6 7 8 9 b a LIFT 6 6 1 6 2 6 el 7804841 02 20012022 INIDENS 95...
Page 97: ...62 B BO 0000279 111 6 3 30 Nm 6 3 1 6 3 2 1 2 1 2 6 el 7804841 02 20012022 INIDENS 97...
Page 131: ...10 3 6 1 2 3 4 5 87 BO 0000208 3 A 2 4 1 5 10 el 7804841 02 20012022 INIDENS 131...
Page 143: ...1 2 3 4 5 6 7 8 9 10 13 el 7804841 02 20012022 INIDENS 143...
Page 348: ...it 13 Smaltimento 348 INIDENS 7804841 02 20012022...
Page 349: ...13 Smaltimento it 7804841 02 20012022 INIDENS 349...
Page 350: ...it 13 Smaltimento 350 INIDENS 7804841 02 20012022...