Press the F2 key or the F3 key until the desired parameter appears,
then press the F4 key to confirm.
Press the F2 – F3 keys to change the value.
press F4 to confirm;
press F1 to exit.
To view/modify the list of settings, it is also possible to connect the
Bluetooth interface to the boiler via the connector X10. Then interface the
handset (SERVICE) to the boiler using the SERVICE TOOL software.
Danger
FOR LOW TEMPERATURE HEATING INSTALLATIONS
MODIFY SETTING CP000 ACCORDING TO THE MAXIMUM
FLOW TEMPERATURE.
Important
The factory settings for certain settings may differ based on the
market the product is destined for.
9.2
List of parameters
Tab.115 Table of parameters
Name
Description
Factory
value
Minimum
Maximum Level
AP001
Operation of contact X15 (also see setting AP098)
1: Contact open —> Heating, domestic hot water and
antifreeze disabled (error code H02.10)
2: Contact open —> Heating, domestic hot water dis
abled (error code H02.09)
3: Contact open —> Heating, domestic hot water and
antifreeze disabled (error code E02.13 with reset re
quest)
2
–
–
Installer
AP002
Manual heating request enabled based on implemen
tation of setting AP026
0: Disabled
1: Enabled
0
–
–
Installer
AP006
Notification of low pressure in the heating installation
[bar]
0.8
0.6
3.0
Installer
AP009
Hours of burner ignition before the maintenance noti
fication with AP010=1
3000
0
51,000
Installer
AP010
Enables/disables maintenance notifications:
0: No notification
1: Customised notification (depending on settings
AP009 and AP011)
2: ABC service notification
0
–
–
Installer
AP011
Hours of electric boiler ignition before the mainte
nance notification with AP010=1
17500
0
51,000
Installer
AP016
CH operation
0: Off
1: On
1
–
–
User
AP017
Domestic hot water (DHW)
0: Off
1: On
1
–
–
User
AP026
Flow temperature setpoint [°C] for manual heat re
quest with AP002=1
40
10
90
Installer
AP056
Outside sensor
0: No outside sensor
1: AF60
2: QAC34 / IFOS
1
–
–
Installer
AP063
Maximum temperature setpoint [°C] in heating and
domestic water mode
80
25
90
Installer
en
9 Settings
188
INIDENS
7804841 - 02 - 20012022
Summary of Contents for INIDENS 20/24 MI
Page 5: ...1 2 3 4 5 1 2 3 4 1 2 3 mm EN 60335 1 0 8 1 5 2 1 bg 7804841 02 20012022 INIDENS 5...
Page 6: ...De Dietrich 1 3 1 3 1 1 3 2 1 3 3 2 2 1 2 2 bg 2 6 INIDENS 7804841 02 20012022...
Page 24: ...13 BO 0000071 5 1 2 3 4 LIFT 10 6 7 8 9 b a LIFT 6 6 1 6 2 bg 6 24 INIDENS 7804841 02 20012022...
Page 26: ...16 BO 0000279 40 6 3 30 Nm 6 3 1 6 3 2 1 2 1 2 bg 6 26 INIDENS 7804841 02 20012022...
Page 42: ...7 7 1 28 7 2 1 2 3 4 5 1 0 1 5 6 7 8 9 7 3 60 mbar 6 kPa bg 7 42 INIDENS 7804841 02 20012022...
Page 72: ...1 2 3 4 5 6 7 8 9 10 bg 13 72 INIDENS 7804841 02 20012022...
Page 76: ...1 2 3 4 5 1 2 3 4 1 2 3 mm EN 60335 1 0 8 bar 1 5 2 bar el 1 76 INIDENS 7804841 02 20012022...
Page 77: ...De Dietrich 1 3 1 3 1 1 3 2 1 3 3 2 2 1 2 2 2 el 7804841 02 20012022 INIDENS 77...
Page 95: ...59 BO 0000071 5 1 2 3 4 LIFT 10 6 7 8 9 b a LIFT 6 6 1 6 2 6 el 7804841 02 20012022 INIDENS 95...
Page 97: ...62 B BO 0000279 111 6 3 30 Nm 6 3 1 6 3 2 1 2 1 2 6 el 7804841 02 20012022 INIDENS 97...
Page 131: ...10 3 6 1 2 3 4 5 87 BO 0000208 3 A 2 4 1 5 10 el 7804841 02 20012022 INIDENS 131...
Page 143: ...1 2 3 4 5 6 7 8 9 10 13 el 7804841 02 20012022 INIDENS 143...
Page 348: ...it 13 Smaltimento 348 INIDENS 7804841 02 20012022...
Page 349: ...13 Smaltimento it 7804841 02 20012022 INIDENS 349...
Page 350: ...it 13 Smaltimento 350 INIDENS 7804841 02 20012022...