4
7
Ambient Humidity
5 ~ 90% (No dew condensation).
Environmental Factor
Requirements
Ambient Temperature
0
0
-10 C~ +50 C;
0
The rated output current should be derated by 2% for every 1 C
0
increase when temperature is over 40 C; When operating in a
small enclosed space such as a cabinet, please strengthen the
cooling to avoid the internal temperature exceeding the
ambient temperature requirements.
Storage Temperature
0
0
-40 C ~ +70 C.
Vibration
Less than 0.5 g.
Altitude
0 ~ 2000 m;
The rated output current should be derated by 1% for every
100 m increase when altitude is over 1000 m.
Installation Site
Indoor use, for outdoor use, protective measures must be
taken;
Install the inverter on flame retardant surface with sufficient
heat dissipation space and good ventilation;
Keep away from electromagnetic radiation sources; No
flammable, explosive, corrosive gases; no radioactive
substances, no flammable substances; no dust, oil mist,
steam;
No direct sunlight
3.2 Installation Method
To ensure good heat dissipation of the product, please install
it vertically. Do not install it horizontally or transversely.
NOTE
2.6 Others
At the end of its design life, the inverter should be disposed
as industrial waste. During incineration, the electrolytic
capacitor may explode and some parts may produce toxic
and harmful gases.
WARNING
3. INSTALLATION AND WIRING
3.1 Installation Instructions
Installation of the inverter according to the installation
environment requirements is the precondition for ensuring
long-term normal and stable operation of the inverter.
NOTE