29
Function
Code
Name
Description
Modi-
ability
Setting
Range
Default
Value
F15.16
Solar Voltage
Measurement
Target
0: DC bus voltage
1: AIN, input terminal of Boost module
0
0,1
F15.17
Tank Full
Alert Delay
Time
Tank full duration time before tank full alert.
Unit: second
10.0s
0.0~
3600.0
F15.18
Tank Full
Reset Start-up
Delay Time
Start-up delay time after
water level returns to normal.
Unit: second
F15.19
Low Sunlight
Frequency
Point
If operating frequency is lower than this set
value, it is judged that the current light
condition is poor.
Unit: Hz
15.00Hz
0.00~
50.00
F15.20
Low Sunlight
Fault Delay
Time
If operating time exceeds this set value under
low sunlight condition, the inverter will stop
and display fault code.
Unit: second
100.00s
0.0~
3600.0
F15.21
Low Sunlight
Fault Reset
Delay Time
Reset delay time after low sunlight fault
Unit: second
F15.22
Given
Reference
Voltage
Unit: V
0 V
0.0~
2000.0
F15.24
Maximum
Reference
Voltage of
MPPT
The maximum reference voltage of MPPT.
Unit: V
600.0s
0.0~
3600.0
180.0s
0.0~
3600.0
F15.23
Minimum
Reference
Voltage of
MPPT
The minimum reference voltage of MPPT.
Unit: V
Determi
ned by
model
0.0~
6553.5
Determi
ned by
model
0.0~
6553.5
F17: State View Function Group
F17.00
Setting
Frequency
Unit: Hz
0.00Hz
0.00~
F00.03
F17.01
Output
Frequency
Unit: Hz
0.00Hz
0.00~
F00.03
F17.02
Slope Given
Frequency
Unit: Hz
0.00Hz
0.00~
F00.03
F17.03
Output
Voltage
Unit: V
0 V
0~1200
F17.04
Output
Current
Unit: A
0.0 A
0.0~
5000
F17.05
Motor
Rotation Speed
Unit: RPM
0 RPM
0~
65535
F17.08
Pump Motor
Power
Unit: the percentage of the pump motor
rated power
0.0%
-300.0~
300